User guide
ATEX/IECEx LED LINEAR LUMINAIRE
INSTALLATION MANUAL
9100-127-1715-00 Rev A
October 2013
Dialight – LED Solutions for Industrial and Hazardous Applications
Tel: 732-919-3119 – Fax: 732-751-5778 – www.dialight.com
Page
1 of 6
LINEAR LED Luminaire for
Hazardous areas
Zones 1,21 & 2,22 Applications
Important Information:
The Dialight Linear fitting is suitable for use in potentially explosive atmosphere in zones 1 and 2 to the
requirements of ATEX Directive 94/9/EC as well as IEC 60079-0, IEC 60079-1, IEC 60079-18, IEC 60079-31
and IEC 60079-7
The product can be used in either wet or dry locations to illuminate areas with potentially explosive atmosphere.
•
WARNING:
DO NOT OPEN WHEN
ENERGISED OR WHEN AN EXPLOSIVE
ATMOSPHERE MAY BE PRESENT
• Do NOT let power supply cords touch
hot surfaces
• Do NOT mount near gas or electric
heaters
• Equipment should be mounted in
locations and at heights where it will
not be subjected to tampering by
unauthorized personnel.
• The use of accessory equipment not
recommended by the manufacturer
may cause an unsafe condition.
• Do NOT use this equipment for other
than intended use.
• For supply connections use wire rated
for at least 96
º
C
SAVE THESE INSTRUCTIONS!!
•
The installation, operation and maintenance must
be carried out by an electrician suitably trained in
hazardous areas.
• The technical data indicated on the LED fixture
are to be observed.
• Changes of the design and modifications to the
LED fixture are not permitted.
• Repairs must only be carried out by a qualified
electrician with hazardous area knowledge.
• Only genuine Dialight replacement parts must be
used when unforeseen repairs are required.
• Observe the national safety rules and regulations
during installation.
• Do not keep these operating instructions inside
the LED fixture.
• Do not open the LED fixture when energized.
• Wait 10 minutes before opening after de-
energizing the LED fixture.
SAVE THESE INSTRUCTIONS!!
IMPORTANT SAFEGAURDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS