Installation Guide

9 | Diamond Kote Building Products Application Guide 6.18
RIGIDMOUNT™
Ensure the penetration is sealed and/or
ashed properly by integrating it into the
weather-resistive barrier. RigidMount
trim
should extend beyond the face of the siding.
Watch our RigidMount
Installation Video.
APPLICATION
Start by preparing for the application
needed. Some cutting maybe necessary
for tment of your specic situation.
Cuts should always be re-sealed with
touch up paint.
A jigsaw works best for cutting, be sure
to cut from the back to keep the nished
surface intact.
Set the mount into position and mark the
weather resistive barrier by using the
nail holes (about 1/2" above the built in
ashing) and the outside edges of the
ange.
Remove the mount and slit the weather
resistive barrier horizontally (slightly
wider than the top ange across those
marks) creating a ap in the weather
resistive barrier.
Next install the RigidMount
by slipping
the top of the nailing ange under the
weather resistive barrier ap.
Set the mount at the correct elevation,
level and then fasten the RigidMount
to
the wall lling every hole in nail ange.
Hand driven galvanized roong nails are
recommended for fastening, such as
1-3/4" Maze STORMGUARD
®
.
Place the adhesive ashing tape over the
top of the RigidMount
ange making
sure to cover nailing holes.
Fold the ap down and seal the slit in the
weather resistive barrier with compatible
building tape.
This single fashion installation helps
shed bulk water out and away from the
structure.
Install siding around the mount and
leave the proper spacing between the
RigidMount placement ange and the
siding.
(Min. 3/16")
Note that the top course of siding should
be cut 3/8" above the built in ashing as
measured from the face of the siding.
Make sure to seal cut edges of siding
with provided touch-up paint. This area
should be left uncaulked.
Finish by applying sealant, starting
approximately 3/4" in from the top
corner and then working your way out,
down the side, and across the bottom.
Also seal the space between the wall
penetrating material and the RigidMount
cut out.
DAP
®
Spec Line 920 sealant which
meets ASTM-C92
0 Specication is
recommended.
TRIM & FASCIA 190, 440, 540 & 2000 SERIES
INSTALLATION
If framing around an existing column, be sure to use pressure
treated lumber in all locations that may be touching concrete,
masonry or decking. Provide adequate framing support for the
trim to be properly fastened. (See diagram 11a)
Be sure to use proper ashing with a minimum 4 inch upper leg.
A secondary water-resistive barrier is recommended as well.
Maintain a 3/8 inch space, and do not caulk, between trim and
ashing. (See diagram 11b)
Maintain a minimum 1 inch clearance between LP SmartSide
products and any surface where water might collect.
(See diagram 11b)
Fasten all trim over 11 inches wide a maximum of every 6
inches o.c. around the perimeter and every 12 inches o.c.
along intermediate supports. For trim under 11 inches wide,
fastener placement and quantity must be consistent with LP®
SmartSide® Trim and Fascia Application Instructions.
(See diagram 11b)
Be sure to prime and paint all expose substrate surfaces and cuts.
TRIM MUST NOT BE IN DIRECT CONTACT WITH MASONRY,
CONCRETE, BRICK, STONE, STUCCO OR MORTAR.
GENERAL REQUIREMENTS (CONTINUED)
Trim mounting blocks should extend beyond the face of the siding.
Prime and paint all cut ends, edges and holes.
On-site assembled:
Use metal Z-ashing with a minimum 4 inch upper leg over the top side of trim mounting block. Leave a minimum 3/8 inch
space above Z-ashing and do not caulk. (See diagram 11d)
Properly integrate the Z-ashing with the housewrap. (See diagram 11c)
Apply fasteners meeting the specications in this document.
Pre-assembled:
Properly integrate the built-in placement ange and ashing with the housewrap. (See diagram 11c)
Fasten the built-in-placement ange to the framing meeting the pre-assembled trim mounting block manufacturers
instructions.
When installing pre-assembled trim mounting blocks, leave proper spacing at the two sides and bottom between the
built-in-placement ange and the siding (minimum 3/16 inch). Seal these spaces with sealant. (See diagram 11d)
Seal the space between the wall-penetrating material or xture and the mounting block cut-out. (See diagram 11d)
11a
C
UTTING
11b
11c 11d
6” o.c.
Column Application
Mounting Blocks for Exterior Fixtures
LP SmartSide Trim & Fascia
11
TRIM & FASCIA 190, 440, 540 & 2000 SERIES
INSTALLATION
If framing around an existing column, be sure to use pressure
treated lumber in all locations that may be touching concrete,
masonry or decking. Provide adequate framing support for the
trim to be properly fastened. (See diagram 11a)
Be sure to use proper ashing with a minimum 4 inch upper leg.
A secondary water-resistive barrier is recommended as well.
Maintain a 3/8 inch space, and do not caulk, between trim and
ashing. (See diagram 11b)
Maintain a minimum 1 inch clearance between LP SmartSide
products and any surface where water might collect.
(See diagram 11b)
Fasten all trim over 11 inches wide a maximum of every 6
inches o.c. around the perimeter and every 12 inches o.c.
along intermediate supports. For trim under 11 inches wide,
fastener placement and quantity must be consistent with LP®
SmartSide® Trim and Fascia Application Instructions.
(See diagram 11b)
Be sure to prime and paint all expose substrate surfaces and cuts.
TRIM MUST NOT BE IN DIRECT CONTACT WITH MASONRY,
CONCRETE, BRICK, STONE, STUCCO OR MORTAR.
GENERAL REQUIREMENTS (CONTINUED)
Trim mounting blocks should extend beyond the face of the siding.
Prime and paint all cut ends, edges and holes.
On-site assembled:
Use metal Z-ashing with a minimum 4 inch upper leg over the top side of trim mounting block. Leave a minimum 3/8 inch
space above Z-ashing and do not caulk. (See diagram 11d)
Properly integrate the Z-ashing with the housewrap. (See diagram 11c)
Apply fasteners meeting the specications in this document.
Pre-assembled:
Properly integrate the built-in placement ange and ashing with the housewrap. (See diagram 11c)
Fasten the built-in-placement ange to the framing meeting the pre-assembled trim mounting block manufacturer’s
instructions.
When installing pre-assembled trim mounting blocks, leave proper spacing at the two sides and bottom between the
built-in-placement ange and the siding (minimum 3/16 inch). Seal these spaces with sealant. (See diagram 11d)
Seal the space between the wall-penetrating material or xture and the mounting block cut-out. (See diagram 11d)
11a
C
UTTING
11b
11c 11d
6” o.c.
Column Application
Mounting Blocks for Exterior Fixtures
LP SmartSide Trim & Fascia
11
Housewrap
Flap
Adhesive
Flashing
Housewrap
Tape
Min. 3/16"
space with
sealant
Min. 3/8" space
(do not caulk)
Min. 3/16"
space with
sealant