Installation Guide

12 | Diamond Kote Building Products Application Guide 6.18
KICK-OUT FLASHING
Note: DO NOT extend the siding or trim into
the kick-out ashing or gutter cut siding.
Install kick-out ashing to direct the
water into the gutter.
A recommended product would be the
DryFlekt
®
Kick-Out Diverters.
Install step ashing with minimum 4"
upper leg.
Properly integrate ashing with the
secondary water-resistive barrier.
Use DryFlekt
®
house wrap, ashing tape,
z-ashing, or other items as needed to
maintain the counter ashing principle.
Maintain the proper clearance between
the end of the gutter and the adjoining
wall to allow for proper maintenance of
the siding.
Paint ALL exposed cut edges; Roof to
wall details.
SPACER FLASHING INSTALLATION
GENERAL
Spacer Flashing is designed to allow for
the minimum clearance requirements
for proper spacing between siding
materials and roong, decks, driveways,
or sidewalks.
SPACER INSTALL:
Spacer Flashing can be installed with
side "D" in moderate contact, or slightly
gapped from the roong, deck, driveway,
or sidewalk.
It is recommended to close the open
end of the Spacer Flashing by making
approximately 1" deep cuts on the
bends (circled in Spacer Diagram) in
from the end of the piece. Then bend the
tabs created from those cuts inward in
this order: B, D, then C.
Fasten through side "A" to the wall every
12-16" on center. Place fastener ¾"
down from the top of side "A".
Properly integrate ashing with the
secondary water-resistive barrier.
Use house wrap, ashing tape, or other
items as needed to maintain the counter
ashing principle.
When installing siding, it's important
to retain 3/8" minimum clearance
between the siding panels and side
"B" of the Spacer Flashing and DO
NOT caulk.
TRIM & FASCIA 190, 440, 540 & 2000 SERIES
PREPARATION
Properly installed ashing materials will help direct water away
from common water collecting areas.
All ashing material shall be metal or another durable material
that under normal outdoor environmental conditions will last for
a period of not less than 50 years.
All ashing materials must have a minimum 4 inch upper leg.
Add a 4 inch wide adhesive ashing to ashing legs less than
4 inches.
Properly integrate ashing with the secondary WRB. Use
housewrap, ashing tape, kick-out ashing, step ashing,
Z-ashing, drip edge, gutters or other items as needed to
maintain the counter-ashing principle.
Install kick-out ashing to direct the water into the gutter.
(See diagram 3a)
Install step ashing that has a minimum 4 inch upper leg.
(See diagram 3a)
Maintain a minimum 1 inch clearance between the end of the
gutter and the adjoining wall to allow for proper maintenance of
the siding. (See diagram 3b)
Do not extend the siding or trim into the kick-out ashing or
gutter.
Prime and paint ALL exposed cut edges of siding and trim.
GENERAL REQUIREMENTS (CONTINUED)
FASTENERS: Minimum 8d (0.113 inch diameter shank), hot-dipped galvanized or stainless steel nail with a 0.270 inch
diameter head. Apply and treat nailing errors as specied by these instructions. (See diagram 3c)
SEALANT: Use an exterior-quality, non-hardening, paintable sealant. Use Class 25 or higher exterior sealant meeting the
ASTM C920 Standard for Specication for Elastomeric Joint Sealants. Follow the sealant manufacturer’s instructions for
application.
PAINT: Exterior-quality 100% acrylic latex paint, specially formulated for use on wood and engineered wood substrates, is
highly recommended. Semi-gloss or satin nish oil or alkyd paints are acceptable. For at alkyd paint, please check with the
coating manufacturer for their recommendations for use on composite wood siding.
3a
C
UTTING
3b
3c
Water Run-O Control
General Application Equipment
WRB
LP SmartSide Trim & Fascia
3
4" min.
step ashing
1" min.
clearance
Kick-out
ashing
ROOF FLASHING DETAIL
TRIM & FASCIA 190, 440, 540 & 2000 SERIES
PREPARATION
Properly installed ashing materials will help direct water away
from common water collecting areas.
All ashing material shall be metal or another durable material
that under normal outdoor environmental conditions will last for
a period of not less than 50 years.
All ashing materials must have a minimum 4 inch upper leg.
Add a 4 inch wide adhesive ashing to ashing legs less than
4 inches.
Properly integrate ashing with the secondary WRB. Use
housewrap, ashing tape, kick-out ashing, step ashing,
Z-ashing, drip edge, gutters or other items as needed to
maintain the counter-ashing principle.
Install kick-out ashing to direct the water into the gutter.
(See diagram 3a)
Install step ashing that has a minimum 4 inch upper leg.
(See diagram 3a)
Maintain a minimum 1 inch clearance between the end of the
gutter and the adjoining wall to allow for proper maintenance of
the siding. (See diagram 3b)
Do not extend the siding or trim into the kick-out ashing or
gutter.
Prime and paint ALL exposed cut edges of siding and trim.
GENERAL REQUIREMENTS (CONTINUED)
FASTENERS: Minimum 8d (0.113 inch diameter shank), hot-dipped galvanized or stainless steel nail with a 0.270 inch
diameter head. Apply and treat nailing errors as specied by these instructions. (See diagram 3c)
SEALANT: Use an exterior-quality, non-hardening, paintable sealant. Use Class 25 or higher exterior sealant meeting the
ASTM C920 Standard for Specication for Elastomeric Joint Sealants. Follow the sealant manufacturer’s instructions for
application.
PAINT: Exterior-quality 100% acrylic latex paint, specially formulated for use on wood and engineered wood substrates, is
highly recommended. Semi-gloss or satin nish oil or alkyd paints are acceptable. For at alkyd paint, please check with the
coating manufacturer for their recommendations for use on composite wood siding.
3a
C
UTTING
3b
3c
Water Run-O Control
General Application Equipment
WRB
LP SmartSide Trim & Fascia
3
1" min.
clearance
2.00
1.00
2.00
1.00
95°
85°
A
B
C
D
Spacer Diagram
3/4"