- Disable input: The output of the analog cam value can be frozen by setting an input to a
specific value.
For this purpose enter the number of the input that shall be used to set the
corresponding analog value to the "Disable value".
- Disable value: Enter the value that shall be displayed if the "Disable input" is active.
This value must not be above the maximum or below the minimum value!
Note: If no cam is programmed fort he used analog output, the "Disable value" is
used as a default value.
- Interpolation: If this option is set to "On", the CamCon interpolates the programmed values
from interpolation point to interpolation point to form a smooth curve.
Interpolation = "Off" Interpolation = "On"
-10V
+10V
90° 180° 270° 360°
-10V
+10V
90° 180° 270° 360°
- Factor: Enter a multiplier factor in percent. If you use e.g. a value of 200%, an input of
10 mA would be displayed as 20mA. An input of 20mA for a 200% factor would
nevertheless cause an overflow.
- Offset: Use this option to set an Offset.
An offset of e.g. 5mA has an input of 10mA displayed as 15mA.
6.6.5.2.2. Programming analog cams
The lower section of the analog cam input is used to program the actual analog cams:
Therefore, each interpolation point (e.g. 180°) is attributed to an analog value (e.g. 9.99V).
The interpolation points can be deleted (DEL), all deleted (Edit) or attributed to new values.
They are displayed in a rising order.