checksum={bcc|crc} (df1fullduplex, df1halfduplex)
Selects the checksum or error-detection method used by the attached 
device. DF1 supports both a 16-bit CRC (“crc”) and an 8-bit Block Check 
Code (“bcc”). Rockwell ‘C*Logix’ processors default to “bcc,” while 
MicroLogix and other PLC families tend to default to “crc.” The Digi 
device default is “crc.”
class={ucmm|cm3} (ethernetip)
Selects either Unconnected ("ucmm") or Connected Class 3 ("cm3") 
explicit messaging for client (ODVA ‘Originator’) connections to remote 
slaves (ODVA ‘Targets’). 
Since only PCCC messages are currently supported, the CIP service 
Exec_PCCC (0x4B) is used to the Rockwell PCCC Object. To 
communicate to a ControlLogix, this option must be set to "cm3," and the 
"connpath" option must be set. The default is "cm3. "
connpath=”path” (ethernetip)
Defines an optional ForwardOpen connection path for client (ODVA 
‘Originator’) connections to remote slaves (ODVA ‘Targets’). To 
communicate to a ControlLogix processor, you will need to enter the slot 
number the form “sN”, where N is the number such as “s0” or “s7”. The 
default is no path or “”.
dontecho={on|off} (chat)
Tells the Digi device to echo ("on") or not echo ("off") bytes directly to 
attached Telnet clients. This compensates for the fact that most systems 
rely on the attached serial device to echo data, but since within the CHAT 
protocol, it holds all client bytes until the end-of-line is detected. The 
default is "off." 
duplex={half|rcv_only|xmt_only} (custom, ascii_import)
Defines message behavior per the port to the server device. 
half
Specifies poll/response behavior. A poll is sent and the Digi device 
waits strictly for a response from the slave device. 
rcv_only
The Digi device only receives data from the attached device. No data 
is transmitted and any received for transmit is discarded. 
xmt_only
The Digi device only send data to the attached device. Any data 
received is discarded. 
The default is "half."
duplicatedetection={on|off} (df1fullduplex, df1halfduplex)
Filters out consecutive requests that have identical command, source, 
and TNS bytes. This behavior is necessary for compliance with the DF1 
specification. The default is "on."