HA3000 20-80 kVA Uninterruptible Power System User Guide Order Number EK-HA32X-UG-002 Digital Equipment Corporation
July 1991 The information in this document is subject to change without notice and should not be construed as a commitment by Digital Equipment Corporation. Digital Equipment Corporation assumes no responsibility for any errors that may appear in this document. Possession, use, duplication, or dissemination of the software described in this documentation is authorized only pursuant to a valid written license from Digital or the third-party owner of the software copyright.
Contents vii About This Manual ix Notes to the User 1 HA3000 SERIES UPS INTRODUCTION 1.1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 SYSTEM DESCRIPTION . . 1.2.1 Rectifier/Battery Charger 1.2.2 Static Inverter . . . . . . . . . 1.2.3 Static Switch . . . . . . . . . . 1.2.4 Manual Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iv Contents 2.4.3 2.4.4 2.4.5 2.4.6 2.4.6.1 2.4.6.2 2.4.6.3 2.4.6.4 2.4.6.5 2.4.6.6 2.4.6.7 2.4.7 2.4.8 2.4.9 3 DISPLAY CONTRAST Menu . . . . . . . . . . . BATT TRANS. TEST Menu . . . . . . . . . . . . BYPASS PROCEDURE Menu . . . . . . . . . . . COMMANDS Menu . . . . . . . . . . . . . . . . . . Rectifier/Battery Charger Start and Stop Inverter Start and Stop . . . . . . . . . . . . . . Resetting Faults Stored in Memory . . . . Synchronous/Nonsynchronous Operation Battery Boost Charge . . . . . . . . . .
Contents v 4 5 6 A HA32C/D/E UPS AUXILIARY CABINET 4.1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1.1 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.1.2 Input Circuit Breaker (CB1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–1 4–1 4–3 4.2 OPERATION . . . . . . . . . . . . . . . . 4.2.1 Input Circuit Breaker (CB1) . . 4.2.2 Input Isolation Transformer . . 4.2.
vi Contents 2–6 2–7 2–8 3–1 4–1 4–2 4–3 5–1 5–2 6–1 6–2 6–3 On Battery Operation Power Flow . . . . . . . . . . . . . . . . . . . . . . . . . . UPS Inverter Shutdown or Major Overload Power Flow . . . . . . . . . . UPS Manual Bypass Power Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . HA32B UPS Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UPS Input Isolation Transformer Configuration . . . . . . . . . . . . . . . .
About This Manual OVERVIEW This manual is intended for users of the HA3000 20-80 kVA series Uninterruptible Power System (UPS). It provides a general introduction to the UPS and available options, and detailed information on system controls and operation. WARNING This unit contains no user-serviceable parts. Only the key-locked doors should be opened to gain access to the circuit breakers. No other doors should be opened or covers removed, for any reason, by untrained personnel.
viii About This Manual The manual covers the following topics: • Chapter 1 provides a general system description of the HA32A UPS and a description of the options available for use with the HA32A UPS. • Chapter 2 provides detailed information on the operation of the system status and control panel, the electromechanical and programmable controls, the UPS monitor and available menus, the automatic and manual operating modes, and the alarm conditions and their causes.
Notes to the User The purpose of the HA3000 UPS is to provide short-term power outage protection for the critical load. The protection time will vary depending upon the size of the load, the charge condition of the batteries, the temperature, and the amount of battery time purchased. For extended power outages, operators wishing to initiate an orderly shutdown should be aware of the battery time available on their system.
1 HA3000 SERIES UPS INTRODUCTION 1.1 GENERAL This chapter introduces the HA3000 series of UPS products rated 20 to 80 kVA. It describes the UPS system, introduces controls and indicators, and describes available options. Figure 1–1 shows the HA32A UPS.
1–2 HA3000 SERIES UPS INTRODUCTION 1.2 SYSTEM DESCRIPTION The HA3000 series Uninterruptible Power System (UPS) is a three-phase on-line interface between a building’s utility power distribution system and the customer’s critical load. The UPS is designed to ensure a continuous flow of clean electrical power to critical loads by addressing common power problems associated with utility ac power. These problems include spikes, electrical noise, sags, brownouts, surges, dropouts, and frequency variations.
HA3000 SERIES UPS INTRODUCTION 1–3 The major components of the HA32A UPS include: • A rectifier/battery charger • A transistorized pulse-width modulated (PWM) static inverter • A continuous-duty rated static switch that automatically transfers the load to and from the bypass ac input source and the UPS inverter output • An internal manual bypass function comprised of three separate switches that allows the critical load to be operated from the utility source • A battery system housed in an externa
1–4 HA3000 SERIES UPS INTRODUCTION 1.2.1 Rectifier/Battery Charger The rectifier/battery charger consists of: • AC Input Circuit Breaker (Q1): The ac input circuit breaker provides mechanical isolation and electrical protection for the input of the UPS. • Input Autotransformer: The input autotransformer is used to match the external ac input source to that required internally for the UPS.
HA3000 SERIES UPS INTRODUCTION 1–5 The three internal manual bypass nonautomatic switches are designated as: • Bypass (MAINS2) Input (Q4S) • UPS Output Isolation (Q5N) • Manual Bypass (Q3BP) For startup or shutdown of the equipment, correct operation of the three switches is shown on the liquid-crystal display (LCD), which is located on the system status and control panel (SS&CP).
1–6 HA3000 SERIES UPS INTRODUCTION 1.3 PROGRAMMABLE CONTROLS AND INDICATORS All HA32A programmable controls (excluding circuit breakers and nonautomatic switches) and indicators are located on the system status and control panel (SS&CP), which is shown in Figure 1–4.
HA3000 SERIES UPS INTRODUCTION 1–7 1.4 BATTERY CABINET Each HA32A UPS requires a separate HA32B UPS Battery Cabinet, which contains batteries having sufficient ampere-hour (A h) capacity to support the UPS and its intended load for the protection time specified. The UPS Battery Cabinet features sealed, maintenance-free, recombination type batteries. The batteries are maintenance-free because they do not require that the electrolyte level or the density of the electrolyte be checked periodically.
1–8 HA3000 SERIES UPS INTRODUCTION transformer secondary voltage is 208 Vac. The transformer supplies both the main ac input (MAINS1), and through the mechanical contactor, the bypass ac input (MAINS2). The transformer also provides complete electrical isolation between the utility line and the input of the UPS (rectifier/battery charger and battery). It also provides extra protection against electrical noise and ground faults.
HA3000 SERIES UPS INTRODUCTION 1–9 1.5.6 DC Ground Fault Detector The HA320-C2 DC Ground Fault Detector is used to detect current flowing from the battery terminals to ground. When a dc ground fault is detected, The UPS main ac input (MAINS1) circuit breaker (Q1) trips, shutting off the rectifier/battery charger, and initiates On Battery operation, which prevents any cascading failures. This fault is indicated by an "ENVIRONMENTAL FAULT" message on the UPS LCD display.
2 HA32A UPS OPERATION 2.1 GENERAL This chapter describes the HA32A system status and control panel (SS&CP), including programmable controls, electromechanical controls, the UPS monitor and available menus, operating modes, and alarm conditions. 2.2 SYSTEM STATUS AND CONTROL PANEL (SS&CP) The SS&CP is located on the upper right portion of the HA32A UPS enclosure. The SS&CP is shown in Figure 2–1, and its elements are described in the following text.
2–2 HA32A UPS OPERATION Liquid-Crystal Display (LCD) The liquid-crystal display (LCD) consists of two lines, 20 characters per line. It is used to display measurements, startup and operating procedures, diagnostics, and alarm messages. The LCD contrast can be adjusted to suit the viewing environment by accessing the DISPLAY CONTRAST Menu (Section 2.4.3). Silence Alarm Key The Silence Alarm key is used to silence the audible alarm.
HA32A UPS OPERATION 2–3 Volts Key The Volts key is used to display submenus that can be used to monitor: • Main ac input voltage (MAINS1)—Phase 1 to 2, 2 to 3, and 3 to 1 input voltages • UPS inverter voltage (UPS output)—Phase 1 to 2, 2 to 3, and 3 to 1 output voltages plus the inverter output frequency • DC bus voltage (battery)—Battery voltage • Bypass ac input voltage (MAINS2)—Phase 1 to 2, 2 to 3, and 3 to 1 input voltages plus the input voltage frequency Figure 2–2 shows how to access the sub
2–4 HA32A UPS OPERATION Current Key The Current key is used to display submenus that can be used to monitor: • Main ac input current (MAINS1)—Phase 1, 2, and 3 input currents • UPS inverter current (UPS output)—Phase 1, 2, and 3 output currents plus the % load for the most heavily loaded phase • Battery current—Negative current (-) indicates battery discharging; positive current (+) indicates battery charging • Bypass ac input current (MAINS2)—Phase 1, 2, and 3 input currents plus the % load for the
HA32A UPS OPERATION 2–5 Menu Key The Menu key is used to return the operator to the Main Menu display. If an error is made while working with the HA32A UPS, pressing the Menu key twice always returns the operator to the Main Menu. Enter Key The Enter key is used to validate an entry or to return to the exited place in the previous menu. Emergency Power Off (EPO) Keys The two EPO keys must be pressed simultaneously to initiate an EPO shutdown.
2–6 HA32A UPS OPERATION 2.3 CONTROLS There are two types of controls for the HA32A UPS: electromechanical and programmable. 2.3.1 Electromechanical Controls The circuit designator for the five electromechanical controls of the HA32A UPS, and the function of each, are listed below. See Figure 2–4 for the location of these controls. Circuit Designator Function Q1 Main ac input (MAINS1) circuit breaker. Applies input voltage to the rectifier/battery charger and provides input current protection.
HA32A UPS OPERATION 2–7 SYSTEM STATUS AND CONTROL PANEL (SS&CP) IDENTIFICATION LABEL Q5N SWITCH Q1 CIRCUIT BREAKER Q3BP SWITCH Q4S SWITCH DOOR LOCK AIR FILTER (BEHIND SCREEN, BENEATH ENCLOSURE) MKV-A2056-91 Figure 2–4 HA32A UPS
2–8 HA32A UPS OPERATION 2.4 UPS MONITOR AND MENUS The UPS monitor is a firmware package that allows the operator to interact with the HA32A UPS. The UPS monitor is menu driven to perform a function. The operator chooses the appropriate menu and then selects the desired function from the menu. NOTE If a UPS Auxiliary Cabinet with an input isolation transformer is installed, circuit breaker CB1 on the UPS Auxiliary Cabinet must be turned on before the UPS can be powered up.
HA32A UPS OPERATION 2–9 The UPS monitor consists of the nine menus that are listed below and described in the following sections. • Menu 1 - START-UP • Menu 2 - INVERTER ON/OFF • Menu 3 - DISPLAY CONTRAST • Menu 4 - BATT TRANS. TEST • Menu 5 - BYPASS PROCEDURE • Menu 6 - COMMANDS • Menu 7 - DIAGNOSIS • Menu 8 - PERSONALIZATION • Menu 9 - COMMUNICATION When the Menu key is pressed the first two menu items are displayed on the LCD.
2–10 HA32A UPS OPERATION 2.4.1 START-UP Menu The START-UP menu is used to return the HA32A UPS to normal operation after it has been completely powered down. The following procedure is for accessing and stepping through the START-UP menu. 1. Press the Menu key and the LCD displays the following: 1 2 START-UP INVERTER ON/OFF 2. Press the 1 key to select menu item number one, START-UP, and the LCD displays the following: CLOSE OUTPUT SWITCH ITEM: Q5N 3.
HA32A UPS OPERATION 2–11 8. To start the inverter press the 1 key and then the Enter key. The following five screens are displayed on the LCD: RESET FAULTS * * CHECKING * * * * * * * COMMAND ACCEPTED END OF PROCEDURE 1 2 START-UP INVERTER ON/OFF 9. After the command to start the inverter is accepted, the inverter starts, the green "inverter" LED goes on, the green "load on bypass" LED goes off, the audible alarm silences, and the flashing red Alarm LED goes off. 10.
2–12 HA32A UPS OPERATION 2.4.2 INVERTER ON/OFF Menu The INVERTER ON/OFF menu is used to stop the inverter and force the static switch to transfer the load to the bypass ac input (MAINS2) power source, or to start the inverter and return the UPS from bypass to normal operation. The following procedure is for accessing and going through the INVERTER ON/OFF menu. 1. Press the Menu key and the LCD displays the following: 1 2 START-UP INVERTER ON/OFF 2.
HA32A UPS OPERATION 2–13 If the inverter is commanded to stop during nonsynchronous operation, the LCD will display the following screens and the inverter must be forced off (see Section 2.4.6). The static switch is inhibited during nonsynchronous operation. When the inverter is forced off, the load will transfer to the bypass ac input (MAINS2) with a 200 to 800 millisecond break. MAINS2 OUT OF SPEC INV STOP INHIBITED INV FORCED STOP 0=NO 1=YES ____ 5. Press the Enter key to return to the menu display.
2–14 HA32A UPS OPERATION 2.4.3 DISPLAY CONTRAST Menu The DISPLAY CONTRAST menu allows the operator to adjust the contrast of the LCD so that it can be easily read under different room lighting conditions. The following procedure is for accessing and going through the DISPLAY CONTRAST menu. 1. Press the Menu key and the LCD displays the following: 1 2 START-UP INVERTER ON/OFF 2. Press the Scroll Down key twice and the LCD displays the following: 3 4 DISPLAY CONTRAST BATT TRANS. TEST 3.
HA32A UPS OPERATION 2–15 2.4.4 BATT TRANS. TEST Menu The BATT TRANS. TEST menu allows the operator to simulate an input power failure by turning off the rectifier/battery charger and allowing the inverter to operate from battery power for two minutes, then returning the UPS to normal operation. This test should be performed periodically to ensure proper UPS operation. This test is only possible if the battery has been charged for at least 10 hours.
2–16 HA32A UPS OPERATION 6. When the test has completed successfully the LCD displays the following: BATTERY OK RESET FAULTS COMMAND ACCEPTED * * CHECKING * * * * * * * 3 4 DISPLAY CONTRAST BATT TRANS.
HA32A UPS OPERATION 2–17 2.4.5 BYPASS PROCEDURE Menu The BYPASS PROCEDURE menu is used to manually transfer the load to the bypass ac input (MAINS2) source without interruption to the load, and for the reverse transfer of the load back to the UPS inverter output. If the bypass ac input (MAINS2) source is out of tolerance, these transfers will result in a 200 to 800 millisecond load interruption and can be performed only with a FORCED STOP command (see Section 2.4.6.4).
2–18 HA32A UPS OPERATION 8. Open the bypass ac input (MAINS2) switch Q4S. The green "load on bypass" LED goes off and the LCD displays the following: OPEN OUTPUT SWITCH ITEM: Q5N 9. Open the output isolation switch Q5N. The LCD displays the following: END OF PROCEDURE 1 2 SW TO MAN BY-PASS RETURN TO UPS WARNING Manual bypass is not intended for maintenance procedures. Contact Digital Services for maintenance procedures. To Return To Inverter 1.
HA32A UPS OPERATION 2–19 5. Press the 1 key and then the Enter key. The LCD displays the following screens: RESET FAULTS * * CHECKING * * * * * * * COMMAND ACCEPTED END OF PROCEDURE 1 2 SW TO MAN BY-PASS RETURN TO UPS 6. When the command to start the inverter is accepted, the inverter turns on, the green "inverter" LED goes on, the green "load on bypass" LED goes off, the audible alarm silences, and the red Alarm LED goes off. 7.
2–20 HA32A UPS OPERATION 2.4.6 COMMANDS Menu The COMMANDS menu is used to initiate the following operations: • Rectifier/battery charger start and stop • Inverter start and stop • Reset faults stored in memory • Synchronous/nonsynchronous UPS inverter operation • Boost charging of the battery • Equalization charging of the battery • Selection of the display language After accessing the COMMANDS menu, use the Scroll Up and Scroll Down keys to select the desired command.
HA32A UPS OPERATION 2–21 2.4.6.2 Inverter Start and Stop Use the following procedure to access the inverter start and stop command. 1. After accessing the COMMANDS menu, press the Scroll Down key until the LCD displays the following: INVERTER 0=STOP 1=START ____ 2. To start the inverter, press the 1 key and then the Enter key. To stop the inverter, press the 0 key and then the Enter key. 2.4.6.
2–22 HA32A UPS OPERATION Use the following procedure to access the synchronous/nonsynchronous operation command. 1. After accessing the COMMANDS menu, press the Scroll Down key until the LCD displays the following: MAINS2 UNSYNCHRON. PASSWORD? __ __ 2. Enter the password by pressing the 1 key, the 9 key, and then the Enter key. The LCD displays the following: MAINS2 UNSYNCHRON. 0=NO 1=YES ____ 3. For synchronous operation, press the 0 key and then the Enter key.
HA32A UPS OPERATION 2–23 3. To apply an equalization charge voltage to the battery, press the 1 key and then the Enter key. Since the inverter must be shut down to apply an equalization charge voltage to the battery, the LCD displays the following. STOP THE INVERTER 0=STOP ____ 4. Press the 0 key and then the Enter key. The inverter stops and equalization charging of the battery begins. 2.4.6.7 Language Selection Use the following procedure to access the language selection command. 1.
2–24 HA32A UPS OPERATION 2.4.7 DIAGNOSIS Menu The DIAGNOSIS menu is used to initiate the standard self-test routine that is built into the UPS. The following procedure is for accessing and going through the DIAGNOSIS menu. 1. Press the Menu key and the LCD displays the following: 1 2 START-UP INVERTER ON/OFF 2. Press the Scroll Down key six times and the LCD displays the following: 7 8 DIAGNOSIS PERSONALIZATION 3.
HA32A UPS OPERATION 2–25 7. When the command to stop the rectifier/battery charger is accepted, the rectifier/battery charger turns off, the green "rectifier/battery charger" LED goes off, and the LCD displays the following: Q1 SWITCH CLOSED? ITEM: Q1 OK=1 __ 8. If the main ac input (MAINS1) circuit breaker (Q1) is closed, press the 1 key and then the Enter key. The LCD displays the following: Q4S SWITCH CLOSED? ITEM: Q4S OK=1 __ 9.
2–26 HA32A UPS OPERATION 13. Press the Enter key and the LCD displays the following screens: ANALOG TEST PCB AQCX ANALOG TEST PCB AQOX START THE CHARGER 1=START ____ 14. Press the 1 key and then the Enter key to start the rectifier/battery charger. The LCD displays the following screens: RESET FAULTS * * CHECKING * * * * * * * COMMAND ACCEPTED 15.
HA32A UPS OPERATION 2–27 17. When the command to start the inverter is accepted, the inverter turns on, the green "inverter" LED goes on, the green "load on bypass" LED goes off, the audible alarm silences, the red Alarm LED goes off, and the LCD displays the following screens: END OF PROCEDURE 6 7 COMMANDS DIAGNOSIS 18. Press the Enter key and the LCD displays the following screen to indicate that the UPS has returned to normal operation.
2–28 HA32A UPS OPERATION 2.4.8 PERSONALIZATION Menu The PERSONALIZATION menu allows access to routines that tailor the operation of the UPS to the specific installation. This menu should be accessed by an authorized Digital Services representative. 2.4.9 COMMUNICATION Menu The COMMUNICATION menu is used to enter the RS-232 interface parameters when required, and should be accessed only by an authorized Digital Services representative.
HA32A UPS OPERATION 2–29 2.5 OPERATING MODES The HA32A UPS has both automatic and manual operating modes. These modes of operation are described in more detail in the following sections. 2.5.1 Automatic Operating Sequences The four automatic operating sequences are described in the following sections. 2.5.1.1 Normal Operation Normal operation is when main ac input (MAINS1) power and bypass ac input (MAINS2) power are available and are within the prescribed tolerances.
2–30 HA32A UPS OPERATION 2.5.1.2 On Battery Operation On battery operation occurs when main ac input (MAINS1) power is lost, if the main ac input (MAINS1) power drops more than 15% below nominal value, or if the rectifier/battery charger circuit fails. The flow of power during on battery operation is shown in Figure 2–6.
HA32A UPS OPERATION 2–31 2.5.1.3 Input Power Restored/Battery Charging As soon as main ac input (MAINS1) power is restored, and the voltage and frequency are within specified tolerances, the UPS returns to normal operation (see Section 2.5.1.1). If the battery reaches its end point of discharge before the main ac input (MAINS1) power is restored, the UPS inverter will shut down and must be manually restarted by following the START-UP menu in Section 2.4.1.
2–32 HA32A UPS OPERATION In the event of a major overload (inrush condition) on the output of the UPS inverter, an immediate transfer of the load to the bypass ac input (MAINS2) power source takes place. The load is automatically returned to the UPS inverter output without interruption when the inrush condition is over. This operating mode allows startup of load devices demanding short-term, high inrush currents, provided that the UPS inverter is synchronized to the bypass ac input (MAINS2) power source.
HA32A UPS OPERATION 2–33 2.5.2.3 UPS Manual Bypass This sequence is used to manually transfer the load to the bypass ac input (MAINS2) power source to bypass the UPS circuits. This sequence should be initiated when problems with the rectifier/battery charger or static switch present the possibility of dropping power to the critical load. This operational sequence can be initiated by following the instructions in the Main Menu, item BYPASS PROCEDURE (see Section 2.4.5).
2–34 HA32A UPS OPERATION 2.6 ALARMS There are two types of alarms in the HA32A UPS; minor and major alarms. The following sections describe the minor and major alarms and contain tables listing the alarms and what they indicate. There are no customer serviceable parts in the UPS equipment. For all repairs, call 1-800-272-2001 or your Digital Services office. 2.6.1 Minor Alarms Minor alarms are those that occur during normal operation but do not interfere with the normal operation of the UPS.
HA32A UPS OPERATION 2–35 Table 2–1 (Cont.) Minor Alarm Messages Alarm Message Problem Indication ENVIRONMENTAL FAULT This indicates that one of eight problems has occurred in the UPS Battery Cabinet, the UPS Auxiliary Cabinet, the UPS CSA Cabinet, or the UPS Distribution Cabinet: 1. The Smoke Detector has detected smoke in the UPS Battery Cabinet. 2. The DC Ground Fault Detector has detected battery currents flowing to ground in the UPS Battery Cabinet. 3.
2–36 HA32A UPS OPERATION Table 2–2 contains the rectifier/battery charger major alarm messages that could appear on the LCD after pressing the Scroll Down key and what each message indicates. Table 2–2 Rectifier/Battery Charger Major Alarm Messages Alarm Message Problem Indication END OF AUTOMY The battery has reached its end point of discharge and the inverter has turned off. MAINS1 OV OR UV The rectifier/battery charger has turned off because of an input ac over/undervoltage condition.
HA32A UPS OPERATION 2–37 Table 2–3 (Cont.) Inverter Major Alarm Messages Alarm Message Problem Indication LEG3 DESATURATION The inverter module for phase 3 is not operating in saturation. PCB POW SUP FAULT Logic power supply board (ALIP) fault. MIN BAT VOLTAGE The inverter has turned off because of low battery voltage. INV OV OR UV The inverter has turned off because of an over/under output voltage condition. THERM UPS OVERLOAD The UPS has shut down because of an overtemperature condition.
3 HA32B UPS BATTERY CABINET 3.1 INTRODUCTION This chapter provides a general description, a description of components, and the specifications of the UPS Battery Cabinet. Figure 3–1 depicts the HA32B UPS Battery Cabinet.
3–2 HA32B UPS BATTERY CABINET 3.1.1 General Description Each HA32A UPS requires a separate HA32B UPS Battery Cabinet(s), which contains batteries having sufficient ampere-hour (A h) capacity to support the UPS and its intended load for the protection time specified. The UPS Battery Cabinets are supplied in compact enclosures similar to the enclosures used for the HA32A UPS.
HA32B UPS BATTERY CABINET 3–3 3.2 OPERATION This section describes standard operating procedures, including battery disconnect circuit breaker QF1 operation, normal operation, and emergency power off (EPO) operation. The UPS Battery Cabinet should be kept in a charged condition for optimum performance over the extended life of the batteries.
4 HA32C/D/E UPS AUXILIARY CABINET 4.1 INTRODUCTION This section describes the HA32C/D/E UPS Auxiliary Cabinets, features, and options. 4.1.1 General Description The HA32C/D/E UPS Auxiliary Cabinet is available in three different configurations for use with the HA32A UPS. The configurations are: 1. Isolation Transformer (HA32D-xx) The isolation transformer can be configured in one of three ways: a.
4–2 HA32C/D/E UPS AUXILIARY CABINET b. Bypass Input Isolation Transformer: The isolation transformer provides complete electrical isolation between the ac input source and the critical load when the UPS is operated on static bypass or manual bypass. See Figure 4–2.
HA32C/D/E UPS AUXILIARY CABINET 4–3 2. UPS Input Harmonic Current Filter (HA32E-Px) The input harmonic current filter limits the amount of current distortion fed back onto the ac input source to less than 10% when the HA32A UPS is operating at full load. 3. Isolation Transformer and UPS Input Harmonic Current Filter (HA32C-xx) The UPS Auxiliary Cabinet can be supplied with both of these UPS options installed within the single Auxiliary Cabinet enclosure.
4–4 HA32C/D/E UPS AUXILIARY CABINET 4.2 OPERATION This section describes standard operating procedures, including operation of the input circuit breaker (CB1), the input isolation transformer, and the input harmonic current filter. 4.2.1 Input Circuit Breaker (CB1) CB1 allows you to manually connect or disconnect the input isolation transformer located inside the HA32C or HA32D UPS Auxiliary Cabinet. CB1 also provides extra protection against overload conditions.
5 HA33D/F UPS CSA CABINET 5.1 INTRODUCTION This section describes the HA33D/F UPS CSA Cabinets, features, and options. 5.1.1 General Description The HA33D/F UPS CSA Cabinet is available in two different configurations for use with the HA32A UPS. The configurations are: 1. CSA Assembly Only (HA33F-Px) A UPS CSA Cabinet with only a CSA assembly is used when 208 Vac utility power is available for the HA32A UPS.
5–2 HA33D/F UPS CSA CABINET 2. CSA Assembly and Isolation/Step-down Transformer Configuration (HA33D-Ex) This configuration of the UPS CSA Cabinet is used when 600 Vac utility power is available for the HA32A UPS. The CSA assembly and the isolation/step-down transformer are both installed within the single UPS CSA Cabinet enclosure. NOTE The HA32C-Ex or HA32D-Ex UPS Auxiliary Cabinet models, or the HA33D-Ex UPS CSA Cabinet are required for use with the HA32A-Ax UPS for systems with a 600 Vac input.
HA33D/F UPS CSA CABINET 5–3 5.2 OPERATION This section describes standard operating procedures, including operation of the input circuit breaker (CB1), the contactor control switch (SW1), and the input isolation/stepdown transformer. During normal operation, the UPS inverter supplies power to the load while the static switch is off and in standby mode.
6 HA32J/K UPS DISTRIBUTION CABINET 6.1 INTRODUCTION This chapter introduces the HA32J/K UPS Distribution Cabinet. The equipment is described, followed by a description of available options. Figure 6–1 depicts the HA32J/K UPS Distribution Cabinet.
6–2 HA32J/K UPS DISTRIBUTION CABINET 6.1.1 System Description The HA32J/K UPS Distribution Cabinet provides the means to distribute power from the HA32A UPS to the user’s intended equipment. The HA32J/K UPS Distribution Cabinet is furnished in an enclosure matching the other HA3000 series equipment. The HA32J/K is designed to attach to the right side of the HA32A UPS, or to either the right side of the HA32C/D/E UPS Auxiliary Cabinet or the HA33D/F UPS CSA Cabinet if these options are purchased.
HA32J/K UPS DISTRIBUTION CABINET 6–3 6.2 OPERATION This section describes the operation of circuit breaker(s) CB1, CB2, and CB3, and the operation of the output circuit breaker(s). Figure 6–3 shows the location of the circuit breakers. OUTPUT CIRCUIT BREAKERS PANELBOARD #2 CIRCUIT BREAKER CB2 OUTPUT CIRCUIT BREAKERS PANELBOARD #1 CIRCUIT BREAKER CB3 CIRCUIT BREAKER CB1 MKV-A2071-91 Figure 6–3 HA32J/K Circuit Breaker Locations 6.2.
6–4 HA32J/K UPS DISTRIBUTION CABINET The branch circuit breaker(s) handle has three positions: 1. OFF or circuit breaker open = handle in the bottom position 2. TRIP or circuit breaker open = handle in the middle position 3. ON or circuit breaker closed = handle in the top position To reset the branch circuit breaker after it has tripped, push the handle down to the OFF position, then move the handle up to the ON position. 6.2.
A SPECIFICATIONS The following are electrical and environmental specifications for the HA32A UPS. AC Input (MAINS1) Ratings Refer to Table A–1 for nominal voltage (Vac) values available. Voltage: As specified, nominal +10%, -15% Frequency: Nominal, ±5% Phases: Three-phase, phase rotation A, B, C Wires: Three, plus equipment ground Current: See Table A–2 Power Factor: 0.
A–2 SPECIFICATIONS Inverter AC Output Ratings Refer to Table A–1 for nominal voltage (Vac) values available. Voltage: Nominal value ±1% for all conditions of line, load, and temperature Frequency: Normally synchronized to the bypass ac input source (when available); otherwise, the output frequency is the nominal value ±0.1% Phases: Three-phase, phase rotation A, B, C Wires: Three or four. The UPS inverter output is normally a wye configuration with the neutral grounded.
SPECIFICATIONS A–3 Environmental Characteristics Temperature: • Operating Range: 0° to 40°C (32° to 104°F), excluding battery • Nonoperating and Storage: -25° to 70°C (-13° to 158°F) NOTE Batteries should be stored only in a fully charged condition at temperatures not exceeding 25°C (77°F). Storage at higher temperatures will reduce storage life and may reduce battery life.
A–4 SPECIFICATIONS The following tables contain the specifications for the HA32A UPS, the HA32B UPS Battery Cabinet, the HA32C/D/E UPS Auxiliary Cabinet, the HA33D/F UPS CSA Cabinet, and the HA32J/K UPS Distribution Cabinet. Table A–1 Standard HA32A UPS Models Model Number Nominal Output Input Rating Voltage kVA/kW 3 (Volts) Input CB Rating (Amps) Output Voltage 3 (Volts) Width mm/in Approx. Weight kg/lbs Heat Loss (Full Load) BTU/hr HA32A-AH 20/16 208 80 208Y/120 800/31.
SPECIFICATIONS A–5 Table A–2 HA32A Currents HA32A-xH HA32A-xK HA32A-xM HA32A-xN 20/16 40/32 60/48 80/64 Output Power Rating kVA/kW Unit Nominal AC Input Current (Amperes) @ Nominal Input Voltage 208 Vac 61.5 121.5 180.4 237.7 220 Vac 58.2 114.9 170.5 224.8 480 Vac 29.3 52.7 78.2 103.0 Unit AC Output and Bypass AC Input Current (Amperes) @ Nominal Voltage (Note 1) Full Load Continuous 208Y/120 55.5 111.0 166.5 222.1 220Y/127 52.5 105.0 157.5 209.9 480Y/277 24.1 48.1 72.
A–6 SPECIFICATIONS Table A–3 UPS Battery Cabinet Model Numbers Circuit Breaker (QF1) Rating in Amperes Width of Battery Cabinet mm/in Approx. Installed Weight kg/lbs Model Number kVA Rating Nominal Protection in Minutes HA32B-AH 20 5 90 800/31.5 530/1,169 HA32B-CH 20 15 90 800/31.5 530/1,169 HA32B-FH 20 30 90 1,143/45.0 905/1,995 HA32B-AK 40 5 125 800/31.5 530/1,169 40 14 125 1,143/45.0 905/1,995 40 30 125 2 x 1,143/45.
SPECIFICATIONS A–7 Table A–5 Interbattery Link Torque Values Manufacturer Model No. Initial Torque Values Subsequent Torque Values Yuasa DM33-12 1.8 N·m (16.3 inch-pounds) 1.2 N·m (10.85 inch-pounds) Yuasa DM55-12 1.8 N·m (16.3 inch-pounds) 1.2 N·m (10.85 inch-pounds) Yuasa DM80-12 1.8 N·m (16.3 inch-pounds) 1.2 N·m (10.85 inch-pounds) Johnson Controls UPS12-95 3.9 N·m (35.0 inch-pounds) 3.4 N·m (30.0 inch-pounds) Johnson Controls UPS12-135 3.9 N·m (35.0 inch-pounds) 3.4 N·m (30.
A–8 SPECIFICATIONS Table A–7 HA32C/D/E UPS Auxiliary Cabinet Electrical Specifications Model Number Output Rating (kVA) Input Voltage (Vac) Input Current (Amps) Output Voltage (Vac) Output Current (Amps) Input CB Rating (Amps) With Input Isolation Transformer and Harmonic Current Filter HA32C-AH 20 208 62 208 62 90 HA32C-BH 20 480 30 208 62 40 HA32C-CH 20 480 30 480 30 40 HA32C-DH 20 220 59 220 59 90 HA32C-EH 20 600 24 208 62 40 HA32C-AK 40 208 122 208 122 17
SPECIFICATIONS A–9 Table A–7 (Cont.
A–10 SPECIFICATIONS Table A–8 UPS CSA Cabinet Weights and Dimensions Output Rating (kVA) HA33D-XX Isolation/Step-Down Transformer and CSA Assembly (kg/lbs) HA33F-XX CSA Assembly Only (kg/lbs) 20 211/465 98/215 40 256/565 98/215 60 333/735 98/215 80 392/865 98/215 Depth of all models: 817 mm/32.18 in Height of all models: 1,402 mm/55.18 in Width of all models: 477 mm/18.
SPECIFICATIONS A–11 Table A–10 UPS Distribution Cabinet Specifications Model Number UPS Output Rating (kVA) Input Voltage (Vac) Maximum Input Current (Amps) Output Voltage (Vac) Maximum Output Current (Amps) Weight (kg/lbs) HA32J-AT 1 20 - 40 208/220 222 208/220 222 225/495 HA32K-AT 1 60 - 80 208/220 222 208/220 222 239/525 HA32J-AH 20 208 55.5 208 55.5 352/775 HA32J-BH 20 480 24.1 208 55.5 352/775 HA32J-DH 20 220 55.5 220 55.
GLOSSARY / Represents "and/or" % Percent; of each hundred. °F Degrees Fahrenheit °C Degrees Centigrade ± Plus or minus Phase Ohms A, B, C Normal sequence of phases in three phase power. AC or ac Alternating current. Ambient air temperature The temperature of the surrounding air. ANSI American National Standards Institute. AWG American Wire Gauge, formerly Brown & Sharp gauge; a standard for sizing crosssectional area of wire conductors, and for measuring sheet metal thickness. B or BAT or BATT.
GLOSSARY–2 BATTERY OV Battery overvoltage. BATTERY UV Battery undervoltage. BREAKER Circuit breaker. British Thermal Unit A unit of heat equal to 252 calories (see Calories below). One British Thermal Unit is defined as the amount of energy required to raise the temperature of one pound of water by one degree Fahrenheit. Btu British Thermal Unit. Btu/Hr British Thermal Units per hour. BYP Bypass.
GLOSSARY–3 CHANGE OK=1 Prompt requesting replacement of subassembly indicated on the preceding LCD line. By entering 1, you indicate to the UPS Monitor that the change has been made. CHARG. (CHARGer) rectifier/battery charger. CHARGE I MAX Prompt for entry of the maximum battery charge current value. CHARGER ACQUISITION FAULT The rectifier/battery charger is not receiving information required for operation.
GLOSSARY–4 DIAGNOSIS Main Menu selection providing access to UPS diagnostic routines for troubleshooting the HA32A UPS. Earth Ground A ground circuit that has contact with the earth. Electrician Refers to an installation electrician qualified to install heavy-duty electrical components in accordance with national and local codes and regulations. Not qualified to maintain or repair electrical or electronic equipment; compare with Technician. EPO Emergency power off.
GLOSSARY–5 GRAD CH STOP Gradual rectifier/battery charger shutdown; a gradual shutdown of the rectifier/battery charger initiated by the closure of an external contact. Hz Hertz; one cycle per second equals one Hertz. I Current. I SENSOR FAULT Indicates a fault on the inverter output current sensor. Input Branch Circuit The input circuit from the building power panel circuit breaker to the UPS module. INV Inverter.
GLOSSARY–6 kW Kilowatt; a measure of real power. LCD Liquid-crystal display. LED Light-emitting diode. LEG Inverter phase. LEG DESATURATION Indicates that the inverter power transistors are not operating in saturation. LEG POWER SUP FAULT Inverter leg power supply fault; indicates a power supply fault on the PC board controlling the transistors of the inverter leg. Load The equipment being protected by the UPS. !LOAD INTERRUPT! Warning that impending action will cause an 0.
GLOSSARY–7 MOV Metal-oxide varistor; a device used to suppress voltage transients (spikes) on an electrical line. NEC National Electrical Code, ANSI/NFPA 70 (latest issue). NFPA National Fire Protection Association. NO. or No. Part number. NOK Not okay. OF Overfrequency. OF/UF Over- or underfrequency. O.T. Out of tolerance. OUTPUT OVERLOAD Indicates that an overload (110%) has occurred.
GLOSSARY–8 PIA Plug-in assembly. Power Factor The ratio (decimal) of real power to apparent power, with current specified as leading or lagging voltage. POWER SUPPLY FAULT Indicates a fault on the control electronics power supply board ALIP. Q1 UPS main ac input (MAINS1) circuit breaker designation. Q3BP Manual bypass circuit breaker designation. Q4S Bypass ac input (MAINS2) circuit breaker designation. Q5N UPS output isolation circuit breaker designation.
GLOSSARY–9 SPEED = BAUDS Programming of the transmission speed in bits per second (baud rate). S.S. or STATIC SW Static switch; used to transfer the load to the bypass ac input (MAINS2) power source without interruption to the load. S.S. PROTECTIVE DEVICE FAULT Indicates a fault on the voltage surge protection circuit connected to the bypass ac input (MAINS2) power source. S.S. THERMO Indicates an overtemperature condition on the SCRs of the static switch assembly.
GLOSSARY–10 UF Underfrequency. UL Underwriter’s Laboratories, Inc. UPS Uninterruptible power system. UV Undervoltage. Vac Volts of alternating current. Vb Battery voltage (in volts). Vdc Volts of direct current. Via By way of. VPC Volts per cell; the measure of the electrical potential of a storage cell, such as a battery. W/O Without. XFMR Transformer.
Index A Alarms, 2–34 major, 2–35 minor, 2–34 B Battery disconnect circuit breaker QF1, 3–3 Battery transfer test, 2–15 BATT TRANS.
2 Index Operating modes manual (Cont.