User guide

2–6 HA32A UPS OPERATION
2.3 CONTROLS
There are two types of controls for the HA32A UPS: electromechanical and
programmable.
2.3.1 Electromechanical Controls
The circuit designator for the five electromechanical controls of the HA32A UPS, and the
function of each, are listed below. See Figure 2–4 for the location of these controls.
Circuit
Designator
Function
Q1 Main ac input (MAINS1) circuit breaker. Applies input voltage to the
rectifier/battery charger and provides input current protection.
Q3BP Manual bypass nonautomatic switch. Allows the bypass ac input to bypass the
UPS and is used in conjunction with Q4S and Q5N.
Q4S Bypass ac input (MAINS2) ON/OFF switch. Applies power to or isolates the
static switch. Used in conjunction with Q3BP and Q5N.
Q5N UPS output isolation switch. Isolates the UPS output and is used in conjunction
with Q4S and Q3BP.
K3N Inverter output contactor. Mechanically isolates the UPS inverter from the static
switch. When the static switch is ON, K3N is open. When the static switch
is OFF, K3N is closed. This contactor makes a loud mechanical sound when it
changes position.
2.3.2 Programmable Controls
The programmable controls are covered in detail in Section 2.4 and include such control
functions as:
Rectifier/battery charger start and stop
Inverter start and stop
Clearing faults
Synchronized/nonsynchronized UPS inverter operation
Output ac voltage adjustment
DC voltage and battery charger current limit adjustments
Boost or equalization charge on battery
Selecting display language
Diagnostic and test routines
Adjusting display contrast