User`s guide

1.2 Specifications
Specifications for the SW300 enclosure are shown in Table 1–1.
Table 1–1 SW300 Specifications
Characteristic Specification
Dimensions (nominal) 838.20 mm (33.00 in) height
476.25 mm (18.75 in) width
482.60 mm (19.00 in) depth
Weight
Cabinet with shipping packaging 106.65 kg (242.00 lb)
Maximum configuration 77.85 kb (178.00 lb)
Agency compliance FCC, UL, CSA, TUV, and CE-mark
Electrical rating 100-120/220-240 V ac, 50/60 Hz, single phase,
12/6 amperes
Operating environment
Temperature +10°C to +40°C (+50°F to +95°F)
Derate 1.8°C for each 1000 m altitude (1.0°F for
each 1000 ft altitude)
Relative humidity 10% to 90% (noncondensing)
Maximum wet bulb temperature: +28°C (+82°F)
Minimum dew point: +2°C (+36°F)
Altitude From sea level to 2400 m (8000 ft)
Air quality
(maximum particle count)
Not to exceed 500,000 particles per cubic foot of
air at a size of 0.5 micron or larger
Nonoperating environment
Temperature -40°C to +66°C (-40°F to +151°F)
(During transportation and associated short-
term storage)
Relative humidity 8% to 95% in original shipping container
(noncondensing); otherwise, 50%
(noncondensing)
Altitude 3600 m (12,000 ft)
Introduction to the SW300 Enclosure 1–3