Turns off the SHELF_OK signal
Activates the audible alarm
Resets the host controller(s)
If one power supply SBB fails, but four or more power supply SBBs are still
functioning, the EMU generates a fault condition and performs the following
actions:
Turns on the Shelf Fault (amber) LED on the front of the EMU
Turns on the Fault (amber) LED located on the upper right corner on the
front of the SW300
Senses cabinet temperature—The EMU senses two different temperatures:
warning and reset state. Warnings take place when the temperature is above
35°C (95°F). The EMU generates a fault condition and performs the following
actions:
Turns on the Temperature (amber) LED on the EMU
Turns on the Fault (amber) LED located on the upper right corner on the
front of the SW300
Turns the dual speed blowers up to high speed
The SW300 is held in a reset state when the temperature is above 50°C
(122°F). The EMU performs the following actions:
Turns off the System OK (green) LED located on the upper right corner
on the front of the SW300
Turns off System OK (green) LED on the EMU
Turns on the Fault (amber) LED on the EMU
Turns off the SYSTEM_POWER_OK signal
Monitors the power supply voltage—The EMU monitors the +12 V dc and +5
V dc cabinet power supplies and if the respective voltage drops below +9.2 V
dc or + 3.9 V dc, the EMU performs the following actions:
Turns off the System OK (green) LED located on the upper right corner
on the front of the SW300
Turns off the System OK (green) LED on the EMU
Turns off the SYSTEM_POWER_OK signal
Activates the audible alarm