User`s guide
For additional information on storage device replacement, see the StorageWorks
Solutions Shelf and SBB User’s Guide.
5.6 Removing an Environmental Monitor Unit
Use the following procedure to remove an EMU:
Note
This component can be removed and installed while power is on. If the
system contains a redundant EMU, then one EMU can be hot swapped
without affecting system operation.
1. Loosen the two captive retaining screws with a flat-blade screwdriver.
2. Use a gentle back-and-forth rocking motion to loosen the EMU from the
backplane.
3. Pull the EMU straight out to disconnect it from the backplane.
5.7 Installing an Environmental Monitor Unit
Use the following procedure to install an EMU:
Note
This component can be removed and installed while power is on.
1. Insert the replacement EMU into the guide slots and push it in until it is
seated.
2. Use a gentle back-and-forth rocking motion to help seat the EMU into the
backplane. Press firmly on the EMU until it is fully seated.
3. Tighten the two captive retaining screws with a flat-blad screwdriver.
5.8 Removing a Controller
Use the following procedure to remove a controller:
Note
This component can be removed and installed while power is on.
1. Perform necessary procedures to shut down the controller and remove
accessory components. See the StorageWorks Array Controllers HS Family of
Array Controllers Service Manual.
2. Loosen the four captive retaining screws with a 3/32-inch Allen wrench
(HSJ-series controllers) or a flat-blade screwdriver (HSD- and HSZ-series).
3. Use a gentle up-and-down rocking motion to loosen the controller from the
backplane.
4. Pull the controller straight out to disconnect it from the backplane and place
it on an approved ESD work surface or mat.
5–6 Removal and Installation Procedures