User`s guide

StorageWorks Replacement Procedures
3.2 Replacing a Blower
3.2 Replacing a Blower
Note
These procedures do not apply to the BA350–LA SBB shelf.
Each StorageWorks shelf has blowers mounted on the rear. Connectors on the
backplane provide the +12 Vdc of power to operate the blowers. When either
blower fails, the shelf status (upper) LED on the power SBB is off and an error
message is passed to the controller or host.
WARNING
Service procedures described in this manual that involve blower removal
or access to the rear of the shelf must be performed only by qualified
service personnel.
To reduce the risk of electrical energy hazard, disconnect the power cables
from the shelf power SBBs before removing shelf blower assemblies or
performing service in the backplane area, such as modifying the SCSI
bus.
Use the following procedure to replace a blower (see Figure 3–2).
1. If you cannot access the rear of the shelf, remove the shelf as described in
Section 3.3.1.
2. Disconnect the power cables to the shelf power SBBs.
3. Use a Phillips screwdriver to remove the safety screw in the upper right
corner or lower left corner of the blower.
4. Press the upper and lower blower mounting tabs together to release the
blower.
5. Pull the blower straight out to disconnect it from the shelf power connector.
6. Align the replacement blower connector and push the blower straight in,
making sure that both mounting tabs lock in place.
7. Replace the safety screw.
8. Replace the shelf as described in Section 3.3.2.
9. Connect the shelf power cables and verify that the shelf and all SBBs are
operating properly by observing the LEDs.
Note
If the upper power supply LED (shelf status) does not come on and all the
shelf power supplies are operating, the second blower may have failed or
the wrong blower was replaced.
3–4 StorageWorks Replacement Procedures