Installation guide

Digital Monitoring Products, Inc.
1912XR Programming
Page 26
The 1912XR panel contains 12 default loop types for use in configuring the system. These loop
types provide the most commonly selected functions for their applications. All loop types except the
Arming loop type can be customized by changing the variable options listed below.
Description of the programmable loop options
Below is a description of the various loop options shown on the table above. For additional
information, read through the Loop Information section of this manual.
Loop Type Defaults - These are complete spellings of the abbreviations used for the loop types.
Type - These are the abbreviations used for the loop types.
Report - A = alarm report, T = trouble report, L = local with no report, - (dash) = no report.
Output - These are the six on-board and 100 off-board relay outputs.
Action - This selects the action of the output: S = steady, P = pulse, M = momentary, and F = follow
Swinger - The loop can be automatically shunted after a programmed number of trips.
Prewarn - This selects the keypad address that sounds the entry prewarn for this loop.
Entry Delay - This is the entry delay timer selected as the default for this loop.
Retard - Provides a programmed retard time before an alarm is initiated from a shorted loop.
Presignal - Provides a keypad tone for loops in retard delay.
Fast Response - Provides a 167ms loop response instead of the normal 500ms response.
Restoral - Allows the loop to send restore reports. N = no, Y = yes, and D = sent at disarming.
Cross Zone - Provides cross zoning with any of the 137 available loops.
Priority - Requires this loop to be in a normal condition before the area can be armed.
13.4A LOOP TYPE SPECIFICATIONS
Message
Output
Action
Message
Output
Action
Message
Output
Action
Message
Output
Action
Swinger
Prewarn
Entry Delay
Retard Delay
Presignal
Fast Response
Restoral
Cross Zone
Priority
Partition Number
LOOP INFORMATION Type Area Disarmed Disarmed Armed Armed
Open Short Open Short
- - NT
Assign Area & Disarmed condition
for NT, DY, EX, A1, A2, AR only DY EX
BDRM
Assign Prewarn and Entry Delay FI PN
for EX only PERIM
EM SV A 1 S A 1 S A 1 S A 1 S N 1 1 N 1 N N N N
Assign Retard and Presignal
for FI, SV, A1, A2, FV only A1 A2 or T to P T to P T to P T to P or
thru
to or
thru
or Y or or
FV AR 1-4 1-8 L 6 M L 6 M L 6 M L 6 M Y 8 4 Y 8 Y or Y Y
Loop Type Defaults Abbr. - F - F - F - F D
NIGHT NT - 0 - - 0 - A 0 - A 0 - Y N Y N N
DAY DY T 0 - T 0 - A 0 - A 0 - Y N Y N N
EXIT EX - 0 - - 0 - A 0 - A 0 - Y 1-8 1 N Y N N
FIRE FI T 0 - A 0 - N N + N Y N N
PANIC PN T 0 - A 0 - N N Y N N
EMERGENCY EM T 0 - A 0 - N N Y N N
SUPERVISORY SV T 0 - A 0 - N N + N Y N N
AUXILIARY 1 A1 T 0 - A 0 - T 0 - A 0 - N N + N Y N N
AUXILIARY 2 A2 T 0 - A 0 - T 0 - A 0 - N N + N Y N N
FIRE VERIFY FV T 0 - A 0 - N N Y N
ARMING AR
100
to
199
100
to
199
100
to
199
100
to
199
INT
– = This function is not enabled for this loop type.
+ = Retard must be YES before Presignal can be selected.
= These loop functions are not available for this loop type.
13-LOOP INFORMATION