Installation guide

Digital Monitoring Products, Inc.
1912XR Programming
Page 31
Additional Loop Programming
The remaining Loop Information you need to specify varies with the different Loop Types. Below is a
list of the remaining information needed and the appropriate section numbers that define each step:
Loop Type Remaining Information Section Numbers
Night, Day, None, programming complete N/A
Panic, Emergency
Exit Prewarn addresses and Entry Delay Sections 13.15 to 13.16
Fire, Supervisory, Retard and Presignal addresses Sections 13.17 to 13.18
Auxiliary 1 and 2
13.15 PREWARN ADDRESSES - At the start of the entry delay, all keypad addresses
selected here display ENTER CODE:-. If you want the prewarn to sound at all
eight addresses, leave the default as shown.
To delete an address, press the matching number on the keypad. To disable
prewarning at all keypads, press a top row key to clear the addresses shown.
Press the COMMAND key when the address selection is complete.
13.16 ENTRY DELAY - Select the entry delay timer for this loop. Entry delay timers 1 to
4 are programmed in section 7.3.
13.17 LOOP RETARD - When you select YES, the loop operates with the retard delay
specified in section 7.5. The retard functions only in loop short conditions.
The loop must remain shorted for the full length of the retard delay before the
panel recognizes its condition. If you select NO, the loop operates without a
retard delay.
13.18 PRESIGNAL ADDRESSES - You can enable any combination of keypad
addresses to sound a presignal tone during the time a loop is in retard delay. The
presignal tone silences when the loop restores or the retard delay expires.
To enable a presignal address, press any top row SELECT key followed by the
number of the keypad address. You can enable the presignal for all eight keypad
addresses. To disable a presignal address press the matching number digit
again. Press the COMMAND key when the address selection is complete. The
Presignal prompt is only displayed when Retard is selected as YES.
ENTRY DELAY: 1
PRESGNL: NONE
PREWARN: 12345678
13-LOOP INFORMATION
RETARD NO