Programming instructions
XR100 Series Programming Guide Digital Monitoring Products
33
Output OptiOns
Output Options
11.1
OUTPUT OPTIONS
Output Options
This section allows you to program panel output options. The panel provides
twoFormCrelays(1and2)andfourswitchedground(opencollector)outputs
numbered3to6.UsetheJ22LX-Busonthepanelandmultiple716Output
ExpanderModulestosupportupto100additionalrelayoutputs.Alternately,when
using the 1100X wireless receiver, 45 wireless outputs are available. Refer to the
XR100SeriesInstallationGuide(LT-0899)forcompleteinformation.
Select from the following output numbers:
•1to6
•450to474—Slowresponsetime*wirelessoutputs(activateswithin15seconds)
•480to499—Fastresponsetime*wirelessoutputs(activateswithin1second)
•500to599—LX-Busoutput
•D1toD8—Keypaddoorstrikerelayforaddresses1-8
•G1toG20—Outputgroup
* The response time of a wireless output is the time it takes for a wireless output
to activate once the panel event occurs. You determine whether a wireless output
is a slow or fast response based on the output number assigned. A slow response
output number extends battery life, but response time may be up to 15 seconds.
A fast response output number responds within 1 second, but reduces battery life.
Refertothespecicwirelessoutputinstallationguidetodeterminebatterylife.
11.2.1
CO OUTS: - - - - - -
Cutoff Output
Outputs1to6canbeenteredheretoturnoffafteratimespeciedinCUTOFF
TIME.Todisablethisoption,pressanySelectkeytoclearthedisplaythenpress
COMMAND. The Cutoff Output displays dashes when no outputs are selected.
11.2.2
CUTOFF TIME: 0
Output Cutoff Time
IfaCutoffOutput(1-6)isassigned,enteraCutoffTimeof1to99minutesforthe
outputtoremainon.Enter0(zero)forcontinuousoutput.
11.3
COMM TRBL OUT: 0
Communication Trouble Output
EntertheoutputnumbertoturnonwhenaDDsystemfailstocommunicateon
three successive dial attempts or if the backup communication line transmits a
report.TheCommunicationTroubleOutputalsoturnsonwhenNETisselected
astheprimarycommunicationmethodandNETcommunicationfailsafterone
minute.WhenNETcommunicationisrestoredtheCommunicationTroubleOutput
automatically turns off.
To manually turn the output off, disarm any area or select Off for the output
numberintheUserMenuOutputsOn/Offsection.Enter0(zero)todisablethis
output.
11.4
FIRE ALR OUT: 0
Fire Alarm Output
Entertheoutputnumbertoturnonwhenaretypezoneisplacedinalarm.The
outputisturnedoffusingtheSensorResetoptionwhilenoadditionalretype
zonesareinalarm.Enter0(zero)todisable.Thisoutputisnotcompatiblewith
Cutoff Outputs.
11.5
FIRE TRB OUT: 0
Fire Trouble Output
Entertheoutputnumbertoturnonwhenaretypezoneisplacedintrouble,
when a supervisory type zone is placed in trouble, or when any system monitor
(AC,Battery,PhoneLine1orPhoneLine2)isplacedintrouble.Theoutputturns
offwhenallreandsupervisorytypezones,orsystemmonitorsarerestoredto
normal.Enter0(zero)todisablethisoutput.Thisoutputisnotcompatiblewith
CutoffOutputs.Thisoutputcanbeconnectedtoalamp,LED,orbuzzerusingthe
DMPModel716OutputExpansionModule.