User's Manual

Digital Monitoring Products XT30/XT50 Installation Guide
12
InstallatIon
Annunciator Outputs
12.1 Description
Thefourannunciatoroutputscanbeprogrammedtoindicatetheactivityofthepanel’szonesorconditions
occurring on the system. Annunciator outputs do not provide a voltage but instead switch-to-ground voltage
from another source. The outputs can respond to any of the conditions listed below:
1) Activationbyzonecondition:Steady,Pulse,Momentary,orFollower 6) Ambushalarm
2) Manuallyfromthekeypad 7) ExitandEntrytimers
3) Communicationfailure 8) SystemReady
4) Armedareaannunciation 9) LatetoClose
5) FireAlarmorFireTrouble
12.2 Harness Wiring
TheopencollectoroutputsareaccessiblebyinstallingtheDMP300Harnessonthe4-pinheaderlabeledJ11.
The output locations are shown below.
Output Color Wire Output Color Wire
1 Red 1 3 Green 3
2 Yellow 2 4 Black 4
12.3 Model 860 Relay Module
ConnectaModel860RelayModuletothepaneltoproviderelaysfortheannunciatoroutputsthatcanbe
used for electrical isolation between the alarm panel and other systems or for switching voltage to control
variousfunctions.Themoduleincludesonerelayandprovidesthreeadditionalsocketsforexpansionofup
tofourrelays.Powerissuppliedtotherelaycoilsfromthepanelkeypadbus.The860mountsinsidethe
panelenclosureusingthe3-holemountingconguration.Plasticstandoffsareprovidedwiththemodulefor
easeofinstallation.A4-wireharnessisalsoprovidedthatconnectstheModel860tothepanel.
Relay Contact Rating: 1Ampat30VDC