InstallatIon
Ethernet Connector J1
14.1 Description
TheEthernetConnector(J1)isavailableontheNetworkversionandconnectsdirectlytoanEthernet
networkusingastandardpatchcable.
14.2 Ethernet LEDs
ThetwoLEDs,locatedontheleftsideoftheJ1EthernetConnector,
indicatenetworkoperation.Thetop,LinkLEDisasteadygreenlight
whenanethernetcableisconnected.Thebottom,ActivityLED
ashesyellowtoindicatemessagesarebeingreceivedortransmitted.
Reset Jumpers J16
15.1 Description
The reset header is located just above the terminal strip on the right side of the circuit board and is used
toresettheXT30/XT50microprocessor.Toresetthepanelwhenrstinstallingthesystem,installthereset
jumper before applying power to the panel. After connecting the AC and battery, remove the reset jumper.
To reset the panel while the system is operational, for example, prior to reprogramming, install the reset
jumper without powering down the system. Remove the reset jumper after one or two seconds.
Afterresettingthepanel,beginprogrammingwithin30minutes.Ifyouwaitlongerthan30minutes,you
must reset the panel again.
XT30/XT50 Panel
J3
Phone Line
Outputs
J11
1
2
3
4
J1
Ethernet
J20
Wireless
Antenna
connection
J7 RJ
Supervision
J24 Celllular
header for
263G
connection
J19 Celllular
Antenna
connection
65555
Momentarily
place the Reset
jumper over both
of the J16 pins to
reset the panel.
J16
Reset
J18
Load
RED
Programming
J8
Figure 9: Panel Showing the Reset Jumper Wires
Flash Load Jumper J18
16.1 Description
ToupdatetheXT30/50panelwithanewsoftwareversion(rule),placejumpersontheReset(J16)and
Load(J18)headers.ConnectaDMP399CablefromtheJ8ProgrammingHeadertoalaptopPCcontaining
therule.Then,removethejumperfromtheReset(J16)headerwhileleavingtheLoad(J18)jumperin
place.
Afterthesoftwareversionisupdated,returnthejumpertoReset(J16),removetheLoad(J18)jumperand
the399cable.ThenremoveReset(J16)jumpertoresumenormalpaneloperation.
Figure 8: J1 Connector and LEDs
J1
Ethernet
Link LED
Activity LED