16
ComPlIanCe
NRTL Listed Specications
19.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstalling
theXT30/XT50inaccordancewithanyoftheANSI/ULburglarystandards.Additionalspecicationsmaybe
required by a particular standard.
19.2 Bypass Reports
ThebypassreportsmustbeprogrammedasYESforallNRTL(NationalRecognizedTestingLaboratory)Listed
burglary applications.
19.3 Current Draw
Thetotalcurrentdrawfromacombinationofauxiliary,smoke,andbelloutputterminalsmustnotexceed
1.6 Amps.
Household Burglar-Alarm System Units ANSI/UL 1023
20.1 Bell Cutoff
The bell cutoff time cannot be less than four minutes.
20.2 Entry Delay
Themaximumentrydelayusedmustnotbemorethan45seconds.
20.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
20.4 Wireless External Contact
Whenused,theExternalContactof1101or1102mustbeprogrammedNormallyClosed.
20.5 Wireless Supervision Time
TheZoneInformationSupervisionTimecannotbesetto0(zero).
20.6 Wireless Audible Annunciation
TheWirelessAudibleoptionmustbeselectedasDAYforresidentialapplications.
20.7 Panel location
Mountpanelinsideprotectedareaorhavetamperswitchinstalledonenclosure.Zone1maybeprogrammed
for Alarm on Tamper.
Digital Burglar Alarm Communicator System Units ANSI/UL 1635
21.1 Entry Delay
The maximum entry delay used must not be more than 60 seconds.
21.2 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
21.3 Test Frequency
TheTestFrequencyoptionmustbeprogrammedtosendareportonceevery24hours.
21.4 Automatic Bell Test
ThisoptionmustbeprogrammedasYES.
21.5 Central Station
DigitalDialerCentralStation(DACT)serviceforcommercialapplicationcanbeprovidedunderUL1635by
addingalistedlocalaudiblesignalapplianceandplacingtheXT30orXT50panelintotheModel350AAttack
ResistantEnclosure.