User's Manual

XT30/XT50 Installation Guide Digital Monitoring Products
19
ComPlIanCe
False Alarm Reduction Programmable Options ANSI/SIA CP-01-2007
(continued)
24.2 Call Waiting
TheCallWaitingdefaultsettingisdisabled.TocanceltheCallWaitingfeature,program*(star)70P
(pause),thestandardtelephonecodeprexthatcancelscallwaiting,intothetelephonenumberstring.
CancelCallWaitingfortelephonelinesthathaveCallWaitingoperationalonthetelephoneline.Seethe
XT30/XT50ProgrammingGuide.
Caution: A call waiting cancel programmed on a non-call waiting telephone line, would prevent
communication to the central station.
24.3 Entry Delay
OnlyuseEntryDelay1.DonotuseEntryDelay2.SeetheXT30/XT50ProgrammingGuide.
24.4 Local Bell
Allnon-rezonessuchasNight,Day,Exit,Aux1andAux2mustbeprogrammedforlocalbellenabledwith
a bell cutoff time set to a minimum of 6 minutes to provide a cancel window of 5 minutes or greater. This
doesnotapplytomanuallyoperatedzonetypessuchasPanicandEmergency.
24.5 Minimum Installation Requirements
SIACP-01-2007minimumsysteminstallationrequirementsincludeanXT30orXT50,alocalBell,andoff
premiseDACTcommunicationtoanSCS-1Rreceiverplusoneofthefollowingcompatiblekeypads.
690,693,790,793SecurityCommand™keypads
7060,7063,7070,7073,7160,7163,7170,or7173Thinline™keypads
7060A,7063A,7070A,or7073AAqualite™keypads
7360or7363Thinline™Iconkeypads
7760ClearTouch™keypad