Installation Guide

1100DH SERIES INSTALLATION GUIDE | DIGITAL MONITORING PRODUCTS 3
Transmitter Supervision TIme
For listed installations, program the transmitter supervision time in panel zone programming as listed in the following
table. Refer to the panel programming guide for complete wireless programming information.
LED INDICATIONS
RF RX Flashing yellow indicates
data is being received from a
transmitter.
RF TX Flashing green indicates data is
being sent to a transmitter.
PANEL RX Flashing yellow indicates data
is being received from a panel.
PANEL TX Flashing green indicates data is
being sent to the panel.
STATUS Solid red indicates memory is
being uploaded. Turns off when
complete.
PWR Solid green indicates there is
power to the wireless receiver.
Table 2: LED Indications
UL Listing Listed Accessories Supervision Time
UL 268 Smoke-Automatic Fire Detectors
1164 Synchronized Smoke Detector
1164NS Smoke Detector with No Sounder
1168 Wireless Smoke/CO/Low Temp Detector
3
UL 365 Police Station Connected Burglar Accessory 1103 Universal Transmitter 60
UL 521 Heat Detectors for Fire Protective Signaling
Systems
1183-135F, 1183-135R Heat Detectors 3
UL 609 Local Burglar Alarm Units and System
Accessory
1103 Universal Transmitter 60
UL 634 Connections and Switches for use with
Burglar Alarm Systems Accessory
1101, 1102, 1103, 1106 Universal Transmitters 60
UL 636 Holdup Alarm Units and Systems Accessory 1142 Two-Button Holdup Transmitter 60
UL 639 Intrusion Detection Units Accessory 1127W, 1127C PIR Motion Detectors 60
UL 985 Household Fire Warning System Accessory
1135 Siren
9060, 9063, 9862 Keypads
240
UL 1023 Household Burglary System Units Accessory
1101, 1102, 1103, 1106 Universal Transmitters
1127W, 1127C PIR Motion Detectors
1135 Siren
1142 Two-Button Holdup Transmitter
9060, 9063, 9862 Keypads
60
UL 1076 Proprietary Burglar Alarm Units Accessory 1103 Universal Transmitter 60
UL 1610 Central Station Burglar Alarm Units Accessory
1103 Universal Transmitter
1135 Siren
9060, 9063, 9862 Keypads
60
UL 2075 Gas and Vapor Detectors and Sensors
1168 Wireless Smoke/CO/Low Temp Detector
1184 Wireless Carbon Monoxide Detector
240
Table 3: Wireless Transmitter Supervision Times
1100DH LED Operation
The six labeled LEDs on the 1100DH PCB display wireless receiver operation
and activity. See Figure 2 for LED locations and Table 2 for LED indications.
House Code Explained
The house code identifies the panel, receiver, and transmitters to each
other. The 1100DH automatically sends the specified house code to wireless
transmitters when transmitter serial numbers are programmed into the
panel.
The 1100DH only listens for transmissions using the specified house code or
the programmed transmitters’ serial numbers.
Note: The 1100R Wireless Repeater and 1100T Wireless Translator follow the Receiver Supervision times for Listed
Accessories.