InstallatIon
Flash Load Button
13.1 Description
TheXTLpanelsoftwarecanbeupdatedviathepanel’sprogramming(PROG)header.Toupdatethepanel
with a new software version, complete the following steps at the protected premise:
1. ConnectaDMP399CablefromtheProgrammingHeadertotheserialportofyourPCoperating
RemoteLinkandcontainingtheXTLRUle.
3. StartRemoteLinkandcreateoropentheXTLcontrolpanelaccountthatmatchesthepaneltobe
updated.
4. SettheConnectionInformationTypetoDirectwithabaudrateof38400andchoosethe
appropriateCOMport.
5. SelectPanel>RemoteUpdate,thenselectthecorrectRUlefortheXTpanelmodel.
6. PressandholdtheLOADbutton(S2),thenpressandreleasetheRESETbutton.
7. ReleasetheLOADbuttonandclick<Update>inRemoteLink.
8. Afterthesoftwareupdateiscompleted,removethe399cableandpresstheRESETbuttonto
resume normal panel operation.