XTL Installation Guide Digital Monitoring Products
9
InstallatIon
Listed Compliance Specications
14.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstalling
theXTLinaccordancewithanyoftheANSI/ULburglarystandards.Additionalspecicationsmayberequired
by a particular standard.
14.2 Use Marking
CommercialCentralStation;HouseholdFireandBurglarWarningSystemControlUnit(Cellular)
14.3 NFPA 72
ThisequipmentshouldbeinstalledinaccordancewithChapter11oftheNationalFireAlarmCode,ANSI/
NFPA72-2002,(NationalFireProtectionAssociation,BatterymarchPark,Quincy,MA02269).Printed
information describing proper installation, operation, testing, maintenance, evacuation planning, and repair
serviceistobeprovidedwiththisequipment.Warning:Owner’sinstructionnotice,nottoberemovedby
anyone except occupant.
14.4 Types Of Service
SuitableforCentralStationStandardLineSecurity.SuitableforHouseholdFireandHouseholdBurglary.Test
weekly.
14.5 Bypass Reports
ThebypassreportsmustbeprogrammedasYESforalllistedburglaryapplications.
14.6 Battery Standby
TheXTLisshippedwithabatteryfor24hourbatterystandbyoperation.
Household Burglar-Alarm System Units
ANSI/UL 1023
15.1 Bell Cutoff
The bell cutoff time cannot be less than four minutes.
15.2 Entry Delay
Themaximumentrydelayusedmustnotbemorethan45seconds.
15.3 Exit Delay
The maximum exit delay used must not be more than 60 seconds.
15.4 Wireless External Contact
Whenused,theExternalContactof1101or1102mustbeprogrammedNormallyClosed.
15.5 Wireless Supervision Time
TheZoneInformationSupervisionTimecannotbesetto0(zero).
15.6 Wireless Audible Annunciation
TheWirelessAudibleoptionmustbeselectedasDAYforresidentialapplications.
15.7 Panel location
Mountpanelinsideprotectedarea.
15.8 Test Frequency
TheTestFrequencyoptionmustbeprogrammedtosendareportatleastonceevery30days.