ComPlIanCe
Central Station Burglar Alarm Units
ANSI/UL 1610
16.1 Standard Line Security
StandardLineSecurityisprovidedwhentheCheck-intimeissetto3minutes.Whenprogrammedfor
StandardLineSecurity,ExitTimeRestartisdisabled.
Note:TheSecureComWirelesstextplanselectedforthepanelshouldmatchorexceedtheprogrammed
MonthlyLimitoradditionalcellularchargesmayapply.
16.2 Remote Disarm
REMOTEDISARMmustbeprogrammedasNO.
16.3 Central Station
MESSAGETOTRANSMITprogrammingforzonesmustnotbesettoLOCAL(L).
Household Fire Warning System
ANSI/UL 985 NFPA 72 Specications
17.1 Bell Output Denition
ThebelloutputoftheXTLpanelmustbeprogrammedtooperatesteadyonburglaryalarmsandtemporal
onrealarms.SeetheXTLProgrammingGuide.
17.2 Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
17.3 Wireless External Contact
Whenused,theExternalContactof1101or1102mustbeprogrammedNormallyClosed.SeetheXTL
ProgrammingGuide.
17.4 Wireless Supervision Time
TheZoneInformationSupervisionTimemustbe3minutesforredevices.SeetheXTLProgrammingGuide.
17.5 Wireless Fire Verication
Whenused,theModel1161and1162wirelesssmokedetectorsmustnotbeprogrammedasFireVerication
(FV)zonetype.SeetheXTLProgrammingGuide.
17.6 Battery Standby
ForULlistedapplications,thepanelmusthave24hourbatterystandbyoperation.
17.7 Test Frequency
TheTestFrequencyoptionmustbeprogrammedtosendareportatleastonceevery30days.