False Alarm Reduction Programmable Options ANSI/SIA CP-01-2007
(continued)
18.2 Entry Delay
OnlyuseEntryDelay1.DonotuseEntryDelay2.SeetheXTLProgrammingGuide.
18.3 Local Bell
Allnon-rezonessuchasNight,Day,Exit,Aux1andAux2mustbeprogrammedforlocalbellenabledwith
a bell cutoff time set to a minimum of 6 minutes to provide a cancel window of 5 minutes or greater. This
doesnotapplytomanuallyoperatedzonetypessuchasPanicandEmergency.
TherequirementsaresupercededbyanyrequirementsforCommercialBurglar,HouseholdFireWarning,or
Household Burglar applications.
18.4 Minimum Installation Requirements
SIACP-01-2007minimumsysteminstallationrequirementsincludeanXTL,an1135WirelessSiren,and
communicationtoanSCS-1Rreceiverplusa9000SeriesWirelesskeypad.