User's Manual
LT-10731.01©2009DigitalMonitoringProducts,Inc.
800-641-4282
www.dmp.com
Made in the USA
INTRUSION•FIRE•ACCESS•NETWORKS
2500NorthPartnershipBoulevard
Springfield,Missouri65803-8877
9425
Battery Life Expectancy
Typical battery life expectancy for DMP Model 1105 wireless transmitters is 5 years. DMP wireless equipment uses
two-way communication to extend battery life.
The following situations can reduce battery life expectancy:
• Ifareceiverisunpluggedornotinstalled.
Note: Transmitters continue to send supervision messages until a receiver returns an acknowledgement.
After an hour the transmitter only attempts a supervision message every 60 minutes.
• Frequenttransmissions,suchasadoorcontactwheremessagesaresenteverytimethedooropensorcloses.
• Wheninstalledinextremehotorcoldenvironments.
The following situation can extend battery life expectancy:
• Extendtransmittersupervisiontimeinpanelprogramming.
• Infrequenttransmissiontrips,suchasawindowthatrarelysendsmessages.
FCC Information
ThisdevicecomplieswithPart15oftheFCCRules.Operationissubjecttothefollowingtwoconditions:
(1) This device may not cause harmful interference, and
(2)thisdevicemustacceptanyinterferencereceived,includinginterferencethatmaycauseundesiredoperation.
Theantennausedforthistransmittermustbeinstalledtoprovideaseparationdistanceofatleast20cmfromall
persons.Itmustnotbeco-locatedoroperatedinconjunctionwithanyotherantennaortransmitter.
Changesormodicationsmadebytheuserandnotexpresslyapprovedbythepartyresponsibleforcompliancecould
void the user’s authority to operate the equipment.
NOTE: ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdigitaldevice,pursuant
topart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmful
interference in a residential installation. This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may cause harmful interference
toradiocommunications.However,thereisnoguaranteethatinterferencewillnotoccurinaparticular
installation. If this equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthereceiverisconnected.
- Consultthedealeroranexperiencedradio/TVtechnicianforhelp.
Specications
Battery
Life Expectancy 5 years (normal operation)
Type 3.0VlithiumCR123A
See Battery Life Expectancy for full details.
FrequencyRange: 903-927MHz
Dimensions
TransmitterCase
1.75”Lx1.6”Wx0.79”H
Standard
MagnetHousing
1.35”Lx0.375”Wx0.425”H
CommercialMagnetHousing
2.25”Lx0.375”Wx0.34”H
Color White
HousingMaterial FlameretardantABS
Patents
U.S.PatentNo.7,239,236
Listings and Approvals
FCCPart15RegistrationIDCCKPC0124
ICRegistrationID5251A-PC0124
Underwriters Laboratories (UL) Listed
ANSI/UL1023 HouseholdBurglarAlarmSystemUnits
ANSI/UL634 ConnectionsandSwitchesforusewith
Burglar Alarm Systems Accessory
ANSI/UL985 HouseholdFireWarningSystem
Accessory
Additional UL Listings for 1105-EOL only
ANSI/UL365 PoliceStationConnectedBurglar
ANSI/UL609 LocalBurglarAlarmUnitsandSystems
ANSI/UL1076 ProprietaryBurglarAlarmUnits
ANSI/UL1610 CentralStationBurglarAlarmUnits
ANSI/UL864 FireProtectiveSignalingSystems