User's Manual
Table Of Contents
- Panel Specifications
- Introduction
- System Components
- Installation
- Primary Power Supply
- Secondary Power Supply
- Bell Output
- Keypad Data Bus
- Smoke and Glassbreak Detector Output
- Burglary Zones
- Powered Zone for 2-Wire Smoke Detectors
- Annunciator Outputs
- Telephone RJ Connector
- Ethernet Connector J1
- Reset Header J16
- Flash Load Jumper J18
- Cellular Connections
- On-Board 1100 Series Wireless Antenna Connection
- Wireless Keypads
- Listed Compliance Specifications
- Household Burglar-Alarm System Units ANSI/UL 1023
- Digital Burglar Alarm Communicator System Units ANSI/UL 1635
- Central Station Burglar Alarm Units ANSI/UL 1610
- Household Fire Warning System ANSI/UL 985 NFPA 72 Specifications
- California State Fire Marshal Specifications
- False Alarm Reduction Programmable Options ANSI/SIA CP-01-2010
- Troubleshooting
- Wiring Diagrams
- Revisions to This Document
XT30/XT50 Installation Guide Digital Monitoring Products
7
InstallatIon
4.2 Mounting Keypads
DMPkeypadshaveremovablecoversthatallowthebasetobemountedonawallorotheratsurfaceusing
the screw holes provided on each corner.
Formountingkeypadsonsolidwalls,orforapplicationswhereconduitisrequired,useaDMP695or696
keypadconduitbackbox.
4.3 Installation Specications
Severalfactorsdeterminetheperformancecharacteristicsofthekeypadbus:thelengthofwireused,the
numberofdevicesconnected,andthevoltageateachdevice.Whenplanningakeypadbusinstallation,
keepinmindthefollowingfourspecications:
1.DMPrecommendsusing18or22-gaugeunshielded wireforallkeypadcircuits.Do not use twisted pair
orshieldedwireforkeypadbusdatacircuits.
2.Onkeypadbuscircuits,tomaintainauxiliarypowerintegritywhenusing22-gaugewiredonotexceed
500feet.Whenusing18-gaugewiredonotexceed1,000feet.Toincreasethewirelengthortoadd
devices, install an additional power supply.
Note:Eachpanelallowsaspecicnumberofsupervisedkeypads.Addadditionalkeypadsinthe
unsupervisedmode.Refertothepanelinstallationguideforthespecicnumberofsupervisedkeypads
allowed.
3.Maximumdistanceforanyonebuscircuit(lengthofwire)is2,500feetregardlessofthewiregauge.
This distance can be in the form of one long wire run or multiple branches with all wiring totaling no
morethan2,500feet.Aswiredistancefromthepanelincreases,DCvoltageonthewiredecreases.
4.Maximumvoltagedropbetweenthepanel(orauxiliarypowersupply)andanydeviceis2.0VDC.Ifthe
voltage at any device is less than the required level, add an auxiliary power supply at the end of the
circuit.Whenvoltageistoolow,thedevicescannotoperateproperly.
Foradditionalinformationrefertothe710InstallationSheet(LT-0310)andortheLX-Bus/KeypadBusWiring
ApplicationNote(LT-2031).
Primary Power Supply
5.1 AC terminals 1 and 2
Connectthetransformerwirestoterminals1and2onthepanel.Usenomorethan70ft.of16gauge,or
40ft.of18gauge,wirebetweenthetransformerandthepaneltodeliveraminimumof15.5VACwhen
500mAofcurrentdrawisusedfromtheauxiliarypowersupplyterminal7.
Always ground the panel before applying power to any devices: The panel must be properly grounded
before connecting any devices or applying power to the panel. Proper grounding protects against
ElectrostaticDischarge(ESD)thatcandamagesystemcomponents.SeeEarthground,intheSecondary
Power Supply section.
5.2 Transformer Types
Thetransformerforthepanelis16.5VAC40VA,whichprovidesupto1.5Ampsofbelloutputcurrent,
500mAofauxiliarycurrent,and100mAofsmokedetectoroutput.UseeithertheModel320wire-inor
321plug-intransformerwiththepanel.Thetotalcurrentavailableislimitedbythetotalbatterystandby
requirements of the installation.
Thetransformermustbeconnectedtoa120VAC60Hzcommercialpoweroutletthatisnotcontrolledbya
wall switch. Never share the transformer output with any other equipment.
5.3 Power LED
WheneitherACtransformerpowerorDCbatterypowerisconnectedtothepanelthePWRLEDshowssteady
green.