User's Manual
Table Of Contents
- Panel Specifications
- Introduction
- System Components
- Installation
- Primary Power Supply
- Secondary Power Supply
- Bell Output
- Keypad Data Bus
- Smoke and Glassbreak Detector Output
- Burglary Zones
- Powered Zone for 2-Wire Smoke Detectors
- Annunciator Outputs
- Telephone RJ Connector
- Ethernet Connector J1
- Reset Header J16
- Flash Load Jumper J18
- Cellular Connections
- On-Board 1100 Series Wireless Antenna Connection
- Wireless Keypads
- Listed Compliance Specifications
- Household Burglar-Alarm System Units ANSI/UL 1023
- Digital Burglar Alarm Communicator System Units ANSI/UL 1635
- Central Station Burglar Alarm Units ANSI/UL 1610
- Household Fire Warning System ANSI/UL 985 NFPA 72 Specifications
- California State Fire Marshal Specifications
- False Alarm Reduction Programmable Options ANSI/SIA CP-01-2010
- Troubleshooting
- Wiring Diagrams
- Revisions to This Document
Digital Monitoring Products XT30/XT50 Installation Guide
18
COMPLIANCE
Central Station Burglar Alarm Units
ANSI/UL 1610
23.1 Central Station
DigitalDialerCentralStation(DACT)serviceforcommercialapplicationcanbeprovidedbyaddingalisted
localaudiblesignalapplianceandplacingtheXT30orXT50panelintotheModel349AAttackResistant
Enclosure.
23.2 Remote Disarm
REMOTEDISARMmustbeprogrammedasNO.
23.3 Central Station
MESSAGETOTRANSMITprogrammingforzonesmustnotbesettoLOCAL(L).
Household Fire Warning System
ANSI/UL 985 NFPA 72 Specications
24.1 Bell Output Denition
ThebelloutputoftheModelXT30/XT50mustbeprogrammedtooperatesteadyonburglaryalarmsand
temporalonrealarms.SeetheXT30/XT50ProgrammingGuide.
24.2 Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
24.3 Household Fire Warning
Recognizedlimitedenergycablemustbeusedforconnectionofallinitiating,indicating,andsupplementary
devices.
24.4 Wireless Supervision Time
TheZoneInformationSupervisionTimemustbe3minutesforredevices.SeetheXT30/XT50Programming
Guide.
24.5 Wireless Fire Verication
Whenused,theModel1161and1162wirelesssmokedetectorsmustnotbeprogrammedasFireVerication
(FV)zonetype.SeetheXT30/XT50ProgrammingGuide.
24.6 Battery Standby
ForULlistedapplications,thepanelmusthave24Hourbatterystandbyoperation.TheModel364battery
shouldnotbeusedforreinstallations.
24.7 Alarm Verication
AlarmVericationmustonlybeenabledonsmokedetectorsthatdonotemployanintegralalarm
vericationfeature.
24.8 Model 860
WhenusingtheModel860RelayOutput,areandnon-redevicemustnotsharearelay.
24.9 Test Frequency
TheTestFrequencyoptionmustbeprogrammedtosendareportatleastonceevery30days.
California State Fire Marshal Specications
25.1 Bell Output Denition
ThebelloutputoftheModelXT30/XT50mustbeprogrammedtooperatesteadyonburglaryalarmsand
temporalonrealarms.