User's Manual

7800 Series Keypad Installation Guide 9
PRELIMINARY
Programming Keypad Options
Kpd Kpd
Opt diag StOp
Keypad Options (KPD OPT)
To program keypad options, press KPD OPT.
CUrrent Keypad
addreSS: 01
Keypad Address
Set the keypad address from 01 to 05 with the XT30, XT50,
XR100 and 01 to 16 with the XR500 Series. The default
address is set at 01. To change the current address, touch
the address display and enter the new address. It is not
necessary to enter a leading zero for addresses 01 to 09.
Keypad MOde:
*SUp UnSUp
Keypad Type
Congure the keypad for either Supervised or Unsupervised
operation. Keypads with zones connected to them must be
supervised and cannot share an address with other keypads.
Unsupervised keypads can operate together sharing the same
address. Zones cannot be used on unsupervised keypads.
To change the current setting, press the SUP or UNSUP. An
asterisk appears next to the selected option.
Note: Unsupervised addresses cannot be used when Device
Fail Output has a programmed value other than zero.
arM paniC KeyS:
*pn *eM *Fi
Arm Panic Keys
Use this option to congure the Panic Icons. To enable
or disable a Panic Icon, touch the icon name: PN (Panic),
EM (Emergency), and FI (Fire). Once the panic icon is
enabled, an asterisk displays next to the description and
the respective Panic icons display for the user. Refer to the
Panic Icon Options section in this document.
SySteM
area a/p h/a hSa
System Mode
Congure the keypad as the same system type selected in
System Options panel programming. Select HSA when zones
are assigned to Bedrooms for the Sleep area to be active.
CLOSing COde
nO yeS
Closing Code
Congure the keypad for the same operation as selected in
panel programming. When YES is selected, a code number
is required for system arming. If NO is selected, a code
number is not required for system arming. Default is NO.
ShOrtCUt Key x:
reSet
Shortcut Keys
Use these options to congure up to three shortcut icons to
display at the bottom of the arming and panic screens. Key
1 default is RESET, Key 2 default is CHIME and Key 3 default
is NONE.
RST (Reset) Sensor (Fire) Reset on all systems
CHM (Chime) Monitor on all systems
CHK (Checkin) Check-in report on XT Series systems
EXIT (Easy Exit) Easy Exit for XT Series Home/Away systems
NONE No shortcut key displayed
ShOrtCUt Key x:
rSt ChM ChK exit
ShOrtCUt Key x:
nOne