APPENDIX
END - PresstheSelectkeydirectlybelowENDtostoptheWalkTest.WhentheWalkTest
endsora20minutetime-outexpires,analSensorResetoccurs.TheSystemTestEnd
message is sent to the receiver along with Verify and Fail messages for each zone under
test.Faultedzonesthendisplayonthekeypad.
Test End Warning
Whennozoneshavebeentrippedandveminutesremainonthe20minuteWalkTest
timer,thekeypaddisplaysTESTENDWARNINGandthekeypadtones.Ifnoadditional
testzonetripsoccur,thetestendsandanalSensorResetautomaticallyoccurs.The
SystemTestEndmessageissenttothereceiveralongwithVerifyandFailmessagesfor
eachzoneunderWALKtest.Faultedzonesthendisplayonthekeypad.
Failed Zones Display
EachzonethatdidnottripatleastonceduringtheWalkTestdisplaysonthekeypad
thatinitiatedthetest.AnyPanic(PN)orSupervisory(SV)24-hourzonethatisfaulted
attheendoftheWalkTestdisplaysatroubleconditionforthatzoneregardlessofthe
message programmed for the open or short condition of the zone and a zone trouble is
senttothereceiver.PresstheCOMMANDkeytodisplaythenextfailedzone.
18.6 Cross Zoning
CautionmustbetakenwhencrosszoningdevicestoensurethattheCrossZoneTimeislongenoughtoallowan
intrudertotripbothdevicesbeforeitexpires.ACrossZoneTimethatistooshortmayallowanintrudertotripthe
devices and allow only a zone fault report be sent to the central station.
WhenaCrossZonedzonetrips,aFAULTreportissenttotheSCS-1RorSCS-VRReceivers.WhentwoCrossZoned
zonestripwithintheCrossZoneTime,bothzonessendALARMsignalstothereceiver.Forexample,ifzones1and
2areCrossZonedzones,andonlyzone1trips,aFAULTreportissenttothereceiverforzone1.Ifzone1tripsand
zone2tripswithintheCrossZoneTime,anALARMreportissenttothereceiverforzone1andzone2.
Note: To operate correctly, all cross-zone zones need to be programmed as the same zone type.
18.7 Zone Type Descriptions
ThissectiondescribesapplicationsforthedefaultzonetypesinZoneInformationprogramming.
NT(NightZone)-ControlledinstantzoneusedforperimeterdoorsandwindowsandinteriordevicessuchasPIRs
andglassbreakdetectors.
DY(Dayzone)-Usedforemergencydoorsorredoorstosoundthekeypadbuzzeranddisplaythezonename
whenthezoneisfaulted.Dayzonesalsowillsendalarmreportstothereceiverduringthesystem’sarmed
periods.
EX(Exitzone)-Initiatestheentrydelaytimerwhenitsassignedareaisfullyarmed.Also,caninitiateanexit
delay timer to allow a user to exit an area after the arming process has started.
PN(Paniczone)-Usedforconnectingtomechanicaldevicesthatallowausertosignalanemergencyalarm.Panic
zones can provide either a silent or audible alarm with or without reporting to a central station receiver.
EM(Emergencyzone)-Theseareusedforreportingmedicalorothernon-panicemergenciestothecentral
station.
SV(Supervisoryzone)-Usedtoprovide24-hourzonesupervision.Typicalapplicationsarehighwater,andlowand
high temperature gauges.
FI (Firezone)-Usedforanytypeofpoweredormechanicalredetectiondevice.Typicalapplicationsarefor
smokedetectors,sprinklerowswitches,manualpullstations,andbeamdetectors.
FV(FireVerifyzone)-Usedprimarilyforsmokedetectorcircuitstoverifytheexistenceofanactualre
condition.WhenaFireVerifyzoneinitiatesanalarm,thepanelperformsaFireReset.IfanyFirezoneinitiates
analarmwithin120secondsafterthereset,analarmisindicated.Ifanalarmisinitiatedafter120seconds,the
cycle is repeated.
A1 and A2(Auxiliary1andAuxiliary2)-ThesezonesaresimilartoaNightzoneandaretypicallyusedtoprotect
restrictedareaswithinaprotectedpremises.Auxiliary2zonesdonotappearintheStatusList.
AR(Armingzone)-Thiszoneallowsyoutoconnectakeyswitchtoazoneanduseittoarmanddisarmthesystem.
TEST END WARNING
SOUTH LOBBY
ZONE: 10 -FAIL