CellComSL
Series Universal Communicator Installation and Programming Guide
6
applIcatIons
3.3 Zone 4 Bell Connection
Zone4(Z4+andZ4-)canbeconnectedtothecontrolpanelbelloutput.Thiszonedetectsanalarmcondition
onthecontrolpanelbymonitoringthevoltageandcadencetimingofthebelloutput.SeeZone4BellCadence
InformationintheAppendixforcadencetiming.Toenablealarmdetectionoperation,Zone4BellConnection
mustbeprogrammedasZoneType(A2)inZoneInformationprogramming.ThetypeofCadencesenttothe
CellComSLCommunicator,theZoneNumber,andtypeofmessagesenttotheSCS-1RorSCS-VRreceiverare
listed below:
BELL CADENCE ZONE NUMBER TYPE OF MESSAGE
Steady ZONE 4 BURGLARY
Pulse or Temporal 3 ZONE 5 FIRE
Temporal 4 ZONE 6 EMERGENCY OR
CARBON MONOXIDE
Note:Zone5and6areautomaticallygeneratedbytheCellComSLSeries,usingZone4’sZonenametosendto
theCentralStation.Zones5and6cannotbepreprogrammedinZoneInformation.
Note:CIDDialerConnectioncannotbeusedwhenusingZone4BellConnection.
Use 18-22 AWG for
Power Supply
connection
Z4 +
Z4 -
DMP Panel
MODEL CellComSL
PROG
+12 G Z1 Z2 Z4-Z4+GZ3 RTO2O1
RB
J8
J9
S3
12 Vdc Aux. Output
+
-
BELL -
12 Vdc BELL +
Use 18-22 AWG for
Power Supply
connection
Z4 +
Z4 -
ADEMCO Panel
MODEL CellComSL
PROG
+12 G Z1 Z2 Z4-Z4+GZ3 RTO2O1
RB
J8
J9
S3
12 Vdc Aux. Output
+
-
BELL -
12 Vdc BELL +
Use 18-22 AWG for
Power Supply
connection
Z4 +
Z4 -
NAPCO Panel
MODEL CellComSL
PROG
+12 G Z1 Z2 Z4-Z4+GZ3 RTO2O1
RB
J8
J9
S3
12 Vdc Aux. Output
+
-
BELL -
12 Vdc BELL +
Use 18-22 AWG for
Power Supply
connection
Z4 -
DSC Panel
MODEL CellComSL
PROG
+12 G Z1 Z2 Z4-Z4+GZ3 RTO2O1
RB
J8
J9
S3
12 Vdc Aux. Output
+
-
BELL -
12 Vdc BELL +
10k ohm
1k ohm
1k ohm
1k ohm
1k ohm
1k ohm
2.2k
ohm
Program Zone 4
DO - Alarm
AO - Alarm
Voltages above 1.4 Vdc
are considered Alarm
Voltages above 1.4 Vdc
are considered Alarm
Voltages above 1.4 Vdc
are considered Alarm
Voltages below 0.7 Vdc
are considered Alarm
Figure 11: Zone 4 Bell Connection