Communication
7.1 Communication
TheCommunicationsectionallowsyoutocongurethecommunicationsettingsforthe
CellComSL
Communicator.AfterchoosingtheCommunicationType,continuethroughthe
list of options.
7.2 Account Number
Entertheaccountnumbersenttothereceiver.
Therangeofaccountnumbersis1to65535.Foraccountnumbersoffourdigitsorless,
you do not have to enter leading zeros. The
c
ommunicatorautomaticallyrightjusties
the account number.
7.3 Transmission Delay
Enterthenumberofseconds(15to45seconds)thecommunicator waits before sending
burglaryalarmreportstothereceiver.Enter0(zero)todisablethisfunction.The
defaultis0.
7.4 Communication Type
The
c
ommunicatorusesCELLcommunicationtoDMPModelSCS-1RorSCS-VRReceivers.
7.5 Test Time
PressCOMMANDtodisplaytheTestTime.Enterthetimeofdaythecommunicator sends
thetestreporttotheSCS-1RorSCS-VRReceivers.Useentriesbetween12:00to11:59
andthenchooseAMorPM.
7.6 Test Days
Enterhowoftenthepaneltestreportissenttothereceiver.Enterfrom1to60days.
Enterzerotodisablethetestreport.Defaultis1(one)day.Theseoptionsonlydisplayif
a test time is entered.
7.7 Cell Check In
Check-inreportsareamethodofsupervisingthepanelforcommunicationwiththe
receiver.
Enterthenumberofminutesbetweencheck-inreports.Selectfrom0or3-240minutes.
Enter0(zero)todisablethecheck-inoption.Defaultis0.
Note:IfCellCheck-inoptionisused,additionalcellchargesmayapply.
7.8 Fail Time
FailTimeallowstheSCS-1RorSCS-VRreceivertomissadenednumberofcheck-ins
before logging that the panel is missing. For example, if CELL CHECKIN is20andFAIL
TIMEis30,theSCS-1RreceiveronlyindicatesaPanelNotRespondingafter30minutes.
The FAIL TIME must be equal to or greater than the CELL CHECKIN minutes: If the
CHECKINis20minutes,theFAIL TIME mustbe20ormore.ThemaximumFAIL TIME is
240minutes.Selectfrom0or3-240minutes.ThedefaultFAIL TIME is240minutes.
7.9 Receiver 1 Programming
Allowsyoutosettheoptionsfortherstreceiverthe
c
ommunicator attempts to
contact when sending reports. The
communicator
supports communication to two
receivers.
7.10 Alarm Reports
YESenablesAlarm,AlarmRestoral,ExitError,andSystemRecentlyArmedreportstobe
senttothisreceiver.DefaultisYES
7.11 Supervisory/Trouble Reports
YESenablesSupervisory,Trouble,TroubleRestoral,ForceArmed,andFaultreportstobe
senttothisreceiver.DefaultisYES.
7.12 Opening/Closing and User Reports
YESenablesOpening/Closing,ScheduleandCodeChanges,andBypassreportsbyuserto
besenttothisreceiver.DefaultisYES.
7.13 Test Report
EnterYEStoenabletheRecallTestreporttobesenttothisreceiver.
7.14 First IP Address
Entertherst(primary)IPaddresswherethe
c
ommunicator sends cell messages. The IP
addressmustbeuniqueandcannotbeduplicatedonthenetwork.Enterall12digitsand
leaveouttheperiods.Forexample,enterIPaddress192.168.0.250as192168000250.
The periods display automatically.
7.15 First IP Port
EntertherstIPportnumbertobeusedinconjunctionwiththeFirstIPAddress.TheIP
portidentiestheportusedtocommunicatemessagestoandfromthecommunicator.
ThedefaultIPPortsettingis2001.
COMMUNICATION
ACCOUNT NO:
XMIT DELAY: 0
COMM TYPE: CELL
CELL TST DAYS: 1
CHECKIN: 0
FAIL TIME: 240
RECEIVER 1 PROG
ALARM NO YES
SPV/TRBL NO YES
O/C USER NO YES
TEST RPT NO YES
FIRST IP ADDR
000.000.000.000
FIRST IP PORT
2001
TEST TIME
00:00 AM