User's Manual

CellComSL
Series Universal Communicator Installation and Programming Guide Digital Monitoring Products
15
remote optIons
Remote Options
9.1 Remote Options
This section allows you to enter the information needed for Remote Command/Remote
Programmingoperation.AdescriptionoftheRemoteOptionsfollows:
9.2 Remote Key
This option allows you to enter a code of up to eight digits for use in verifying the
authority of a receiver to perform a remote command/programming session. The
receivermustgivethecorrectkeytothe
c
ommunicator beforebeingallowedaccess.All
CellComSL
CommunicatorsareshippedfromthefactorywiththeRemoteKeypresetas
blank.
ToenteranewRemoteKey,pressanySelectkeyandenteranycombinationofupto8
digits.Thenumbersyouenterappearasasterisks.PressCOMMAND.
9.3 Remote Disarm
EnterYEStoenablethe
c
ommunicatortobedisarmedremotely.SelectingNOdisables
remote disarming.
System Reports
10.1 System Reports
This function allows you to select which reports the
c
ommunicator sends to the receiver.
10.2 Opening/Closing Reports
NO-NoOpening/ClosingReportsaresent.
YES-SendsOpening/ClosingReportsforeachprogrammedarea.
10.3 Zone Restoral Reports
This option allows you to specify whether the communicator sends zone restoral reports
and when they will be sent.
NO-Restoralreportsarenotsentbythecommunicator.
YES-Thecommunicator
always sends zone restoral reports at the time the zone
restores from an alarm or trouble condition.
DISARM-Thecommunicator sends zone restoral reports when a zone that has
restored from an alarm or trouble is disarmed. Twenty-four hour zones send restorals
immediately.
System Options
11.1 System Options
This section allows you to select system wide parameters used in the operation of the
c
ommunicator system.AdescriptionofeachSystemOptionfollows:
11.2 Entry Delay 1
Entertheentrydelaytimeforallexittypezonesprogrammed.WhenanarmedExittype
zone is faulted, the area must be disarmed before the entry delay expires or a fault will
bedetected.AllBurglarytypezonesaredelayedalongwiththeExitzone.Entrydelay
timescanbefrom30to250seconds.Defaultis30seconds.
11.3 Exit Delay
EntertheExitDelaytimeforallExittypezones.Whentheexitdelaytimestarts,all
activityonexitandburglaryzonesisignoreduntiltheexitdelayexpires.DuringExit
Delay,ifanexitzonetrips,thenrestores,andtripsagain,theExitDelaytimerrestarts.
Thisrestartcanoccuronlyonce.Exitdelaytimescanbefrom30to250seconds.
Defaultis60seconds.
ExitErrorOperation:Atarming,whenanentry/exitzone(EX)isfaultedattheendof
theexitdelaythenazonealarmandanExitErroraresenttothereceiver.
11.4 Cross Zone Time
Enterthetimeallowedbetweenzonefaults.Whenazoneprogrammedforcrosszoning
faults, the
c
ommunicatorbeginscountingdowntheCross-ZoneTimeenteredhere.Ifthe
same zone or another cross-zoned zone faults within this time, an alarm report is sent to
the receiver.
IftheCross-ZoneTimeexpireswithoutthesecondzonefault,onlyazonefaultreport
fromtherstzoneissenttothereceiver.TheCross-ZoneTimecanbefrom4to250
secondsinonesecondincrements.Enter0(zero)todisabletheCross-ZoneTime
feature.SeetheAppendix-CrossZoning.
REMOTE OPTIONS
RMT KEY:
DISARM NO YES
SYSTEM REPORTS
O/C RPTS NO YES
RESTORAL YES
NO YES DISARM
SYSTEM OPTIONS
ENTRY DLY 1: 30
EXIT DELAY: 60
CRS ZONE TM: 0
system reports
system optIons