Installation and programming Guide IComsl™ Series Universal Alarm Communicator
FCC NOTICE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
Table of Contents Table of Contents Description........................................................................................................................ 1 What is Included................................................................................................................ 1 System Components.............................................................................. 1 1.1 1.2 1.4 1.5 1.6 1.7 Terminals (J9)........................................................................
Table of Contents 7.20 7.21 7.22 7.23 7.24 7.25 7.26 Supervisory/Trouble Reports...................................................................................12 Opening/Closing and User Reports..........................................................................12 Test Report............................................................................................................12 First IP Address..................................................................................................
Table of Contents 13.4 Automatic Arming..................................................................................................18 13.4.1 Bad Zones.............................................................................................................18 13.5 Automatic Disarming..............................................................................................18 Zone Information................................................................................. 18 14.1 14.2 14.3 14.
Table of Contents 18.5 Cross Zoning..........................................................................................................28 18.6 Z-Wave Information................................................................................................28 18.7 Zone 4 Bell Cadence Information.............................................................................28 Remote Arming/Disarming for Ademco Vista Control Panels..................................................
Introduction iComSL™ Series Universal Alarm Communicator Description The iComSL™ Series Alarm Communicator provides a fully supervised alarm communication path for any burglary or residential fire control panel. The iComSL Series can be connected to a control panel’s dialer output and used to capture Contact ID messages based on SIA DC-05-1999.09-DCS. The iComSLC has a built-in ethernet port to connect to a network and send messages to DMP Model SCS-1R or SCS-VR Central Station Receivers.
system components Open-Collector Outputs The two outputs, terminals O1 and O2 (see Figure 1), can be programmed to indicate the activity of the zones or conditions occurring on the system. Open-Collector outputs do not provide a voltage but instead switch-toground the voltage from another source. Maximum voltage is 30Vdc @ 50 mA.
Installation Mounting the iComSL Series Communicator 2.1 Selecting a Location Install the communicator away from metal objects. DO NOT MOUNT THE iCOMSL SERIES COMMUNICATOR INSIDE OR ON A CONTROL PANEL METAL ENCLOSURE (See Figure 5). Control Panel Metal Enclosure Figure 5: Suggested Mounting Locations Mounting the communicator on or near metal surfaces impairs Z-Wave wireless performance.
Applications S N Applications S1 The iComSL Series Communicator can be used in a variety of applications: 3.1 RESET S1 CID Dialer Connection S2 LOAD J26 MODELthe control panel to the iComSL to capture Contact Directly connect the telco phone line (tip and ring) from S2 iComSLC ID messages that are based on the SIA communication standard DC-05-1999.09-DCS. These messages are then formatted into a Serial 3 message and sent to a DMP Model SCS-1R or SCS-VR Receiver.
Applications 3.3 Zone 4 Bell Connection Zone 4 (Z4+ and Z4-) can be connected to the control panel bell output. This zone detects an alarm condition on the control panel by monitoring the voltage and cadence timing of the bell output. See Zone 4 Bell Cadence Information in the Appendix for cadence timing. To enable alarm detection operation, Zone 4 Bell Connection must be programmed as Zone Type (A2) in Zone Information programming.
remote arming/disarming Remote Arming/Disarming 4.1 DMP Virtual Keypad App / Virtual Keypad Browser Using a Smartphone with the DMP Virtual Keypad App or using a computer with the Virtual Keypad Browser (www.myvirtualkeypad.com), you can connect to the iComSL Series Communicator to arm Areas, turn Outputs on and off, and add, edit or remove Users. When using the iComSLCZ, you can control Z-Wave devices, Favorites and Rooms.
Programming Programming the iComSL Series Universal Alarm Communicator 5.1 Before You Begin Before starting to program, we recommend you read through the contents of this guide. The information in this document allows you to quickly learn the programming options and operational capabilities of the iComSL Series Universal Alarm Communicator. After this Introduction, the remaining sections describe the functions of each programming menu items along with their available options.
Programming 5.5 Special Keys The following special keys/areas are common to all DMP keypads. COMMAND (CMD) Key Pressing the COMMAND key allows you to go forward through the programming menu and through each step of a programming section. As you go through the programming, the keypad display shows any current programming already stored in the communicator memory. If no change is required for an option, press the COMMAND key to advance to the next step.
Programming 5.7 5.8 Entering Non-Alpha Characters To enter a space in an alpha entry, press the 9 digit key followed by the third Select key/area. The three characters on the 9 digit key are Y, Z, and space. You can also enter the following characters: – (dash), . (period), * (asterisk), and # (pound sign) using the 0 (zero) key and the four Select keys/areas from left to right. For example, to enter a – (dash), press the 0 (zero) key and then the left Select key/area.
initialization Initialization 6.1 Initialization Initialization This function allows you to set the communicator’s programmed memory back to the factory defaults in preparation for system programming. After you select YES to clear a section of memory, the communicator asks if you are sure you want to clear the memory. This is a safeguard against accidently erasing part of your programming. No memory is cleared from the programming until you answer YES to the SURE? YES NO prompt.
communication Communication 7.1 COMMUNICATION 7.2 Account NO: 7.3 Xmit Delay: 7.4 Comm Type: 7.5 Communication The Communication section allows you to configure the communication settings for the iComSL Communicator. After choosing the Communication Type, continue through the list of options. Account Number Enter the account number sent to the receiver. The range of account numbers is 1 to 65535. For account numbers of four digits or less, you do not have to enter leading zeros.
communication 7.16 SECOND IP Addr Second IP Address Enter the second IP address where the communicator sends network messages. The IP Address must be unique and cannot be duplicated on the network. Enter all 12 digits and leave out the periods. For example, enter IP address 192.168.0.250 as 192168000250. The periods display automatically. 000.000.000.000 7.17 SECOND IP PORT Second IP Port 2001 Enter the second IP port number to be used in conjunction with the Second IP Address.
Messaging setup Messaging Setup 8.1 Messaging Setup MESSAGING sETUP This section allows you to enter the information needed to send and receive messages directly to and from the panel via Email using network communication. The Destination addresses allow up to 48 characters to be entered. System Name is displayed with initial caps.
messaging setup 8.12 SMTP SERVER - 8.13 SMTP PORT: 25 8.14 SMTP USERNAME - 8.15 SMTP PASSWORD - 8.16 FROM EMAIL - SMTP Server Enter the SMTP (Simple Mail Transfer Protocol) Server name. The SMTP Email server is responsible for sending the Email to its destination. An example SMTP Email server name is: mail.somedomain.com. The domain should be the Email server that will provide Email support for your alarm customers.
remote options 9.1 Remote Options Remote Options Remote Options This section allows you to enter the information needed for Remote Command/Remote Programming operation. A description of the Remote Options follows: 9.2 RMT Key: Remote Key 9.3 Disarm NO This option allows you to enter a code of up to eight digits for use in verifying the authority of a receiver to perform a remote command/programming session. The receiver must give the correct key to the communicator before being allowed access.
system options 11.5 Pwr Fail Hrs: 1 11.6 SWGRBYPS TRIPS: 11.7 Rst SByp 11.8 Time Chg NO 2 Yes Swinger Bypass Trips Enter the number of times (1-6) a zone can go into an alarm or trouble condition within one hour before being automatically bypassed. Bypassed zones are automatically reset when the area they are assigned to is disarmed. All 24-hour zones are reset when any area of the system is disarmed. A programming Stop operation restores a bypassed zone.
Output Options Output Options 12.1 12.2 Output Options OUTPUT Options This section allows you to program communicator output options. Switched Ground (open collector) outputs are available using terminals O1 and O2 as the ground and your burglary control panel for power. Select from outputs 1 or 2. Cutoff Outputs Co Outs: - - This option allows you to define the operation of the two on-board outputs.
area information 13.4 Auto Arm NO Yes 13.4.1 Bad Zones: Byp Byp Forc Ref 13.5 Auto Dis NO Yes Automatic Arming Select YES to allow this area to arm automatically according to the opening and closing schedule. At arming, faulted zones are handled according to the option selected in Bad Zones. If a Closing report is sent, the user number is indicated as SCH on the SCS-1R or SCS-VR Receivers. Select NO to disable automatic arming for this area. Default is NO.
zone information 14.6 Area: 1 - - - - - Tgl 14.7 Style: Tgl Arm DIs Step Mnt 14.8 Next Zn? NO Yes 14.9 Alarm Action . . . 14.10 Disarmed Open 14.11 MSG: alarm A T l - Arming Zone Assignment This option specifies the areas to be armed by the Arming Type zone. Press the appropriate number keys on the keypad to assign areas 1 to 6. When disarmed, all areas are disarmed. Style This option specifies the style for the arming/disarming operation. The default for STYLE: is TGL (Toggle).
zone information 14.12 Output No: 0 14.13 Action: STD Pls Mom FLW 14.14 Swgr Byp NO Yes 14.15 Crs Zone NO YES 14.16 RECEIVER ROUTING NORMAL NORM 1 2 BOTH 14.17 Zone No: - Digital Monitoring Products 20 Output Number You can specify any of the outputs/Favorites on the communicator to be activated by a zone condition. The output/Favorite can be activated regardless of the report to transmit or whether or not the zone is programmed as local.
stop Stop 15.1 Stop Stop At the STOP prompt, pressing any Select key allows you to exit the programmer function of the communicator. When selected, the communicator performs an internal reset and exits the programmer. set lockout code Set Lockout Code 16.1 Set Lockout Code Set Lockout Code Pressing COMMAND at the Stop prompt displays SET LOCKOUT CODE.
z-wave setup Z-Wave Setup (Model iComSLCZ Only) Your system may include a DMP Z-Wave controller. The Z-Wave controller allows short range radio control of Z-Wave devices that you or your installation company may provide such as lighting control modules, thermostat controls, doors, and garage doors. Z-Wave Setup allows you to program the system to control the Z-Wave devices. You may control your Z-Wave devices from your Smartphone using the DMP Virtual Keypad App or with the Virtual Keypad Browser.
z-wave setup 17.4 STATUS of Z-Wave Devices 1. 2. 3. 4. Access the User Menu. Press COMMAND until ZWAVE SETUP? displays. Press any Select key. The keypad displays ADD LIST REMOVE. Select LIST to display DEVICE LIST and the first Z-Wave device stored. Press the COMMAND key to advance through the list of Z-Wave devices. 5. Press any Select key to display DEVICE RENAME STATUS. 6. Select STATUS to confirm radio communication with the Z-Wave device. 7.
z-wave setup 17.8 17.9 ADD Devices to FAVORITES 1. Access the User Menu. 2. Press COMMAND until ZWAVE SETUP? displays. 3. Press any Select key. The keypad displays ADD LIST REMOVE. 4. Press COMMAND again to display FAV XFER OPT. Select FAV and FAVORITE NUMBER: - is displayed. 5. Enter a Favorite number between 1 and 20 and press COMMAND. 6. The Favorite number and name displays. Press COMMAND and the Favorite Name and ADD EDIT REMOVE displays. 7.
z-wave setup 17.10 EDIT Devices in FAVORITES 1. Access the User Menu. 2. Press COMMAND until ZWAVE SETUP? displays. 3. Press any Select key. The keypad displays ADD LIST REMOVE. 4. Press COMMAND again to display FAV XFER OPT. Select FAV and FAVORITE NUMBER: - is displayed. 5. Enter a Favorite number between 1 and 20 and press COMMAND. 6. The Favorite number and name displays. Press COMMAND and the Favorite Name and ADD EDIT REMOVE displays. 7.
z-wave setup 17.13 Optimize (OPT) Select Optimize (OPT) to update communication with all Z-Wave devices. Optimize can be used to re-establish communication after a Z-Wave device has been moved to a different location. When OPTIMIZE is selected, the iCom makes three attempts to communicate with each Z-Wave device. Z-Wave devices that fail to communicate during the optimize process are not removed from iCom programming. 1. Access the User Menu. 2. Press COMMAND until ZWAVE SETUP? displays. 3.
Appendix Appendix This section of the iComSL Series Universal Alarm Communicator Installation/Programming Guide provides additional zone and system information. 18.1 False Alarm Reduction System Recently Armed report The System Recently Armed report (S78) is sent when a burglary zone goes into alarm within two minutes of the system being armed. 18.2 Diagnostics Function The communicator contains a Diagnostics function that allows you to check Panel Settings.
Appendix test zone trips occur, the test ends and a final Sensor Reset automatically occurs. The System Test End message is sent to the receiver along with Verify and Fail messages for each zone under WALK test. Faulted zones then display on the keypad. Failed Zones Display South Lobby Zone: 10 18.5 -Fail Cross Zoning Each zone that did not trip at least once during the Walk Test displays on the keypad that initiated the test.
Appendix Remote Arming/Disarming for Ademco Vista Control Panels The following steps describe how to configure the iComSL to arm and disarm an Ademco Vista control panel from a schedule or remotely from the Virtual Keypad App, Virtual Keypad Browser, MyAccess™, or RemoteLink™, using the Remote Arming Output. See Figure 17: Ademco Vista 20P to iComSL. 1. Locate output 17 on the Ademco control panel (far left pin on the 7 pin header located in the middle of the PCB).
Ademco Vista 20P Appendix OUT 18 OUT 17 +12 AUX GND Ademco Vista 20P to iComSL 1 2 3 4 5 (USE SA4120XM-1 CABLE) 6 7 8 SYNC BLACK COM DATA RED + - VISTA 20P ONLY 17 18 19 20 HI 16 LO 15 HI 14 LO 13 HI 12 LO 11 HI 10 LO + 9 HI 8 LO 7 HI - 6 LO 5 HI + 4 LO 3 HI 2 LO 1 21 22 23 24 25 TIP RING TIP RING (BROWN) (GRAY) (GREEN) (RED) S1 RESET J1 S2 Remote Arming out to Keyswitch Arming Zone Armed Output of Vista to CellComSL Arming Zone LOAD J8 B R
Appendix Ademco Vista 20P ECP to iComSL 1 2 3 4 OUT 18 +12 AUX GND OUT 17 Ademco Vista 20P 5 (USE SA4120XM-1 CABLE) 6 7 8 SYNC BLACK COM DATA RED + - VISTA 20P ONLY 17 18 19 20 HI 16 LO 15 HI 14 LO 13 HI 12 LO 11 HI 10 LO + 9 HI 8 LO 7 HI - 6 LO 5 HI + 4 LO 3 HI 2 LO 1 21 22 23 24 25 TIP RING TIP RING (BROWN) (GRAY) (GREEN) (RED) S1 RESET J1 S2 LOAD J8 B R S3 J9 Figure 19: Ademco Vista 20P ECP to iComSL iComSL Series Universal Communicator
Certifications Nominal 12Vdc 210 mA 210 mA 5.5”W x 3.75”L x 1” H White Ordering Information iComSLC California State Fire Marshal (CSFM) iComSL FCC Part 15 ID: CCKPC0159 IC: 5251A-PC0159 ETL Listed ANSI/UL 1610 ANSI/UL 1023 ANSI/UL 985 Central Station Burglar Household Burglar Household Fire Warning (CID Capture) 800-641-4282 INTRUSION • FIRE • ACCESS • NETWORKS www.dmp.com 2500 North Partnership Boulevard Designed, Engineered and Assembled in U.S.A.