18.1 False Alarm Reduction
System Recently Armed report
TheSystemRecentlyArmedreport(S78)issentwhenaburglaryzonegoesintoalarmwithintwominutesofthe
system being armed.
18.2 Diagnostics Function
The communicator containsaDiagnosticsfunctionthatallowsyoutocheckPanelSettings.TouseDiagnostics,
reset the
communicator
,entertheDiagnosticscode2313(DIAG).
Panel Settings
PressingatoprowkeyallowsaccesstotheMACAddress,SerialNumber,Model,andFirmwareVersion.
Serial Number
This number is the communicator serial number. Reference this number for communicator date-of-manufacture,
hardwareversion,etc.PressanytoprowSelectkeytodisplaytheSerialNumber.
Model Number
This menu option displays the model number of the
communicator
.
Firmware Version
Thismenuoptiondisplaysthermwareversionnumberofthe
communicator
and date it was released.
Z-Wave Test Option
This feature allows the installer to test
iComSL
CZcommunicationwithZ-Wavedevices.
Asuccessfultestindicatesaresponsefromadevice.PressanytoprowSelectkeyto
viewtheZ-WaveDeviceList.
PressCOMMANDtoadvancethrougheachZ-WavedeviceandpressanytoprowSelect
keytobeginthetestonthedevicedisplayed.
The name of the device displays above the device number. The current number of
successful communications followed by the total number of attempts displays to the
rightofthedevicenumber.Theteststopsafter99attempts.
PressCOMMANDtoviewthenalnumberofsuccessfulcommunications.
Contact ID Recvd
ThisdisplaysDTMFdigitsdialedfromtheburglarycontrolpanel.
Exiting the Diagnostics program
PresstheCOMMANDkeyuntilSTOPdisplays.PressanySelectkey.ThekeypadreturnstotheStatusListdisplay.
18.3 Using the 984 Command Function
WhennotintheProgrammingMenu,thefunction984+COMMANDcanbeenteredatthekeypad,andaremote
options menu appears. This menu contains the following options:
18.4 Using the Walk Test
Thecommunicatorprovidesawalktestfeaturethatallowsasingletechniciantotestallthezonesonthe
system.ConducttheWalkTestwithin30minutesofresettingthecommunicator.TheWalkTestautomatically
endsifnozonesaretrippedfor20minutes.TEST IN PROGRESSdisplaysatallkeypads.Whenveminutes
remain, TEST END WARNINGdisplays.IfanyareasarearmedtheWalkTestdoesnotstartandSYSTEM ARMED
displays.
Walk Test
ToconducttheWalkTest,resetthecommunicatorbymomentarilypressingtheRESET
button.Fromthekeypad,enterthecode8144.ThekeypaddisplaysWALK TEST. If
thesystemismonitored,thesystemsendsaSystemTestBeginreporttotheCentral
Station.Allprogrammedzonesareincludedinthetest.
Trip Counter for Walk Test (STD)
DisplaysthenumberofzonetripsduringtheWalkTest.
• Eachtimeaselectedzonetrips,thekeypadbuzzes.
END - PresstheSelectkeydirectlybelowENDtostoptheWalkTest.WhentheWalkTest
endsora20minutetime-outexpires,analSensorResetoccurs.TheSystemTestEnd
message is sent to the receiver along with Verify and Fail messages for each zone under
test.Faultedzonesthendisplayonthekeypad.
Test End Warning
Whennozoneshavebeentrippedandveminutesremainonthe20minuteWalkTest
timer,thekeypaddisplaysTESTENDWARNINGandthekeypadtones.Ifnoadditional
TEST ZWAVE
DEVICE LIST:
HALLWAY LIGHT
HALLWAY LIGHT
LIGHT 02 0/0
HALLWAY LIGHT
99/99 SUCCESSFUL
WALK TEST
WALK TEST
TRIPS: XXX END
TEST END WARNING