User's Manual
iComSL
Series Universal Communicator Installation and Programming Guide Digital Monitoring Products
1
IntroductIon
iComSL™ Series Universal Alarm Communicator
Description
The
iComSL
™SeriesAlarmCommunicatorprovidesafullysupervisedalarmcommunicationpathforanyburglary
orresidentialrecontrolpanel.TheiComSLSeriescanbeconnectedtoacontrolpanel’sdialeroutputand
usedtocaptureContactIDmessagesbased on SIA DC-05-1999.09-DCS.TheiComSLChasabuilt-inethernet
porttoconnecttoanetworkandsendmessagestoDMPModelSCS-1RorSCS-VRCentralStationReceivers.
The
c
ommunicator also provides four input zones and two open-collector outputs for connection to burglary or
residentialrecontrolpaneloutputsandzones.TheiComSLSeriesCommunicatorZone4allowsaconnection
to the bell output of an existing burglary control panel. The communicator operates in a variety of applications:
CIDDialerConnection,Zones1-4InputConnections,orZone4BellConnection(SeeApplicationsonpage5).The
iComSL
CZ™AlarmCommunicatorincludesanonboardZ-Wavecontrollerforhomeautomationapplications.
What is Included
The
iComSL
SeriesUniversalAlarmCommunicatorincludesthefollowing:
• PCBwithEnclosure
• HardwarePack
System Components
1.1 Terminals (J9)
Power Connection Terminals
PowerisprovidedfromtheNominal12Vdcauxiliaryoutputoftheburglarycontrolpanel.
OBSERVEPOLARITY(SeeFigure1andBacklitLogo)
Using18-22AWGwire,connectthe
communicator
terminal+12tothepositiveterminalonthe
control panel
auxiliary output
.
ConnectthecommunicatorterminalG(Ground)tothenegativeterminalonthecontrolpanelauxiliaryoutput.
Control Panel Standby Power
Duringapoweroutage,theiComSLdrawspowerfromthecontrolpanel’sbackupbattery.TheiComSLmustbe
included in the standby battery calculations for the control panel.
Zones 1-4
TerminalsZ1toZ3,G(Ground),Z4+andZ4-providefourzonestoconnecttoindividualrelayoutputson
thecontrolpanel.Zone4(Z4+andZ4-)canbeconnectedtothecontrolpanelbelloutput.SeeZone4Bell
Connection.
Figure 1: iComSL Series Communicator
RB
J8
J1
RESET
LOAD
S1
S2
S3
J9
system components