PROGRAMMING INTRODUCTION
19.8 Programming Menu
Accessing the Programmer
To access the programmer function of the XTLplus:
Use a standard LCD keypad, connect to the PROG header and set the keypad to Address 1.
Press the RESET button for two seconds.
Enter the code 6653 (PROG).
The keypad displays: PROGRAMMER.
Remove the hardwired keypad when programming is completed.
You are now ready to start programming the XTLplus panel. Pressing the COMMAND key scrolls you through
the programming menu items listed below.
Menu Item Section in This Manual Menu Item Section in This Manual
Initialization 20
BellOptions 29
FastProgram 21 OutputOptions 30
Communication 22
OutputSetup 31
NetworkOptions 23 Area Information 32
MessagingSetup 24 Zone Information 33
Device Setup 25 Stop 34
RemoteOptions 26
Set Lockout Code
35
System Reports 27 Appendix 36
SystemOptions 28
To select a section for programming, press any select key when the name of that section displays on the
keypad. The detailed instructions for each programming step are found in sections 20 to 35 of this manual.
19.9 Programmer Lockout Codes
Although the XTLplus panel allows access to Programming without a lockout code, it is available to program
one to restrict programming access to authorized individuals only. You can do this by using SET LOCKOUT
CODE at the end of the programming menu.
Installing a lockout code
1. After entering the Programmer menu, the keypad displays PROGRAMMER. Press the COMMAND key until
SET LOCKOUT CODE is displayed (after STOP).
2. Press any select key. At the ENTER CODE: - display, enter a 1- to 5-digit programmer lockout code.
Press COMMAND.
3. The display shows ENTER AGAIN. Enter the same lockout code again and press COMMAND. The display
shows CODE CHANGED. The new code number must now be entered before the Programmer menu can
be accessed.
The lockout code should be written down and kept in a secure place with access limited to authorized
persons only.
Lost Lockout Code requires factory reset: If you lose or forget the lockout code, the panel must be sent
back to the factory to be reset. There is no eld option for gaining access to the panel without a valid
lockout code.
19.10 Reset Timeout
The XTLplus has a feature that requires you to enter the Programmer within 30 minutes of resetting the
panel. After 30 minutes, if you attempt to program by entering the 6653 (PROG) code, the keypad displays:
RESET PANEL. You must reset the panel and enter the program code within the next 30 minutes.
If you are already in the Programmer and do not press any keys on the programming keypad for 30 minutes,
the panel terminates programming. All data entered up to that point is saved in the panel’s memory.
To exit the panel’s Programmer you must use the Stop function. The STOP option is the second to the last
option in programming. The programming session is then terminated and the keypad returns to the
Status List.