SYSTEM REPORTS
27.7 Ambush
YES allows an ambush report to be sent any time user code number one is entered
at a keypad. Selecting NO disables the ambush report and allows user code number
one to operate the same as all other codes.
27.8 Late To Open
Enter 1-240 as the number of minutes to elapse that the system may remain armed
after the opening time of a schedule without sending a Late To Open message. If
the system continues to be armed after the Late to Open minutes expire, a Late To
Open message is sent to the central station. Default is 0, which disables the Late
To Open option.
27.9 Early To Close
Enter 1-240 as the number of minutes that the system can be armed prior to the
scheduled closing time. If the system is armed prior to the Early to Close minutes,
an Early To Close message is sent to the central station. Default is 0, which
disables the Early to Close option.
System Options
28.1 System Options
This section allows you to select system wide parameters used in the operation of
the XTLplus panel. A description of each System Option follows:
28.2 System
This congures the panel as either a six Area system, an All/Perimeter system
(Perimeter/Interior), or a Home/Away system (Perimeter, Interior, and Bedrooms).
Zones must be assigned to Bedrooms for the area to be active.
Wireless zones in an Area or All/Perimeter system resound the trouble buzzer every
four hours when zone trouble or low battery is displayed.
28.3 Closing Code
When YES is selected, a code number is required for system arming. If NO is
selected, a code number is not required for system arming. Default is NO.
28.4 Closing Check
Select YES to enable the panel to verify that all areas have been armed after a
schedule expires. If the Closing Check nds any areas disarmed past the scheduled
time, all keypads emit a steady beep and display CLOSING TIME!. The user must
extend the schedule or arm the system within 10 minutes or a Late to Close
message is sent to the central station. Default is NO.
28.5 Entry Delay 1
Enter the entry delay time for all exit type zones programmed to use Entry Delay
1. When an armed Exit type zone is faulted, the keypad prewarn tone begins
sounding. ENTER CODE: - and the name of the zone causing the Entry Delay
displays on all keypads.
When the rst digit of a code is entered, the prewarn tone stops at the keypad.
If, within ve seconds, a valid user code is not entered or an invalid user code is
entered, the prewarn tone begins sounding again. Fifteen seconds must elapse
before entering a digit silences the prewarn tone again.
The area must be disarmed before the entry delay expires or an alarm is detected.
All Burglary type zones in all areas are delayed along with the Exit zone.
Entry delay times can be from 30 to 250 seconds. Repeat the above for Entry Delay
2 if it is being used. Default is 30 seconds for Entry Delay 1.
Note: Specic Exit Error operation is based on the Entry Delay used (1 or 2) with an
EX type zone. See Exit Delay.
28.6 Exit Delay
Enter the Exit Delay time for all Exit type zones. When the exit delay time starts,
all activity on exit and burglary zones is ig nored until the exit delay expires. The
keypad displays the Exit Delay time countdown and annunciates the Exit Delay
tone at 8 second intervals until the last 10 seconds when annunciation is at 3
second intervals. The exit de lay can be from 45 to 250 sec onds. Default is 60
seconds. During Exit Delay, if an exit zone trips, then restores, and trips again, the
AMBUSH NO YES
LATETOOPEN
MINUTES: 0
EARLYTOCLOSE
MINUTES: 0
SYSTEM OPTIONS
SYSTEMOPTIONS
SYSTEM:ALL/PERIM
AREA A/P H/A
CLSCODE NO YES
CLSCHK NO YES
ENTRYDLY1: 30
ENTRYDLY2: 60
EXITDELAY: 60