Digital Monitoring Products XTLplus Installation and Programming Guide
48
COMPLIANCE
Household Fire Warning System
ANSI/UL 985 NFPA 72 Specications
40.1 Bell Output Denition
The bell output of the Model XTLplus must be programmed to operate steady on burglary alarms and
temporal on re alarms.
40.2 Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
40.3 Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes for re devices.
40.4 Wireless Fire Verication
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verication
(FV) zone type.
40.5 Battery Standby
For listed applications, the panel must have 24 Hour battery standby operation. The Model XTL+BAT3500
battery should be used for re installations.
40.6 Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.