1168 CO/Smoke Combo Unit Installation and Programming Guide 13
MOUNTING GUIDELINES
In addition to NFPA 72, use the following location guidelines to optimize performance and
reduce false alarms. Refer to Figure5.
Place ceiling-mounted smoke detectors in the center of a room/hallway at least
4inches from walls and partitions. If a ceiling is sloped, peaked, or gabled, place
the detector 3 feet from the highest-point. If mounting to suspended ceiling tile,
the tile must be secured with an appropriate fastener across ceiling panel supports.
Place wall-mounted smoke detectors at least 4 inches below the ceiling.
Mount smoke detectors on a firm, permanent surface.
Place in environmentally-controlled areas with a temperature range between
40° and 100° F (4.4° and 37.8° C) and the humidity is between 0 and 90%
non-condensing.