Programming Guide

1168 CO/Smoke Combo Unit Installation and Programming Guide 28
COMPLIANCE SPECIFICATIONS
Specifications
Battery Life Expectancy At least 1 year
Battery Type 4 x 3.0 V, CR123A Lithium; Panasonic CR123A only
Sensitivity UL Limits .9 to3.50%/ft; ULC Limits .9 to 3.08%/ft
Audible Signal 85dBA
Frequency Range 905-924 MHz
Dimensions 16.002cm Diameter x 4.19cm Thick
6.3in Diameter x 1.65in Thick
Tamper Cover
Operating Temperature 32°F - 100°F; 0°C - 38°C
Storage Temperature 14°F - 158°F; -10°C - 70°C
Relative Humidity 20 - 95% RH (Agency Compliance is 93% max),
Non-condensing
Color White
Patents
U.S. Patent No. 7,239,236