Programming Guide

18 1134 Installation and Programming Guide | Digital Monitoring Products, Inc.
ACTIVATE ZONE 3 REQUEST TO EXIT
Selecting YES activates the zone 3 Request to Exit (REX) option.
Selecting NO allows standard zone operation on zone 3. Default
setting is NO.
Connect a motion sensing device or a mechanical switch to zone 3 to
provide REX capability to the system.
When zone 3 shorts, the on-board Form C relay activates for the
programmed number of seconds. See Zone 3 REX Strike Time.
During this time, the user can open the protected door to start the
programmed zone 2 bypass entry/exit timer. After the programmed
number of seconds, the relay restores the door to its locked state.
The 1134 module provides a bypass-only option for REX on zone 3.
When zone 3 OPENS from a NORMAL state, only a bypass occurs: the
on-board relay does not activate. This bypass-only option uses two
methods of REX.
The first REX device provides the programmed bypass entry/exit
timer. The second REX unlocks the door.
ACTIVATE ZONE 3
REX? NO YES