Programming Guide

Digital Monitoring Products, Inc. | 1134 Installation and Programming Guide 23
SITE CODE DISPLAY
You can program up to eight 8-digit site codes. The site code range is
0-16,777,214.
In the keypad display, enter site code 1 and press CMD. The display
will ask for site code 2 followed by site code 3 and so on. When you
have selected the site code you want to change, press CMD.
NUMBER OF USER CODE DIGITS
The 1134 module recognizes user codes from 4-12digits long. Press
any top row select key or area to enter a user code digit length. This
number must match the user code number length being programmed
in the panel. Default is 5.
All bits are read and converted into a decimal number string. The
number string is left padded with ‘0’ if needed for long user code
lengths. When selecting ‘4’ the right digit is dropped and the next
four sent.
Example: # decoded 1234567
10 digits 0001234567
5 digits 34567
4 digits 3456
SITE CODE 1:
NO OF USER CODE
DIGITS: 5