Programming Guide

24 1134 Installation and Programming Guide | Digital Monitoring Products, Inc.
NO COMMUNICATION WITH PANEL
Define the relay action when communication with the panel has not
occurred for 5seconds. Default is OFF. Press any select key or area to
change the default relay action:
Press the first select key or area to choose OFF (Relay Always O) —
The relay and Wiegand LED do not turn on when any Wiegand string
is received. OFF does not aect any REX operation. If communication
is lost during a door strike, the relay remains on for the door strike
duration but turns o at the end of the door strike timer.
Press the second select key or area to choose SITE (Accept Site
Code) — Door access is granted when the Wiegand site code string
received matches any site code programmed at SITE CODE DISPLAY.
Refer to REQUIRE SITE CODE for more information.
Press the third select key or area to choose ANY (Any Wiegand Read)
— Access is granted when any Wiegand string is received.
Press the fourth select key or area to choose ON (Relay Always On) —
The relay is always on.
Press CMD to display the next action.
Press the first select key or area to choose LAST (Keep Last State)
— The relay remains in the same state and does not change when
communication is lost.
NO COMM WITH PNL
OFF SITE ANY ON
NO COMM WITH PNL
LAST