LED SURVEY
The 1134 provides a Survey LED capability to
allow one person to confirm communication with
the wireless receiver while the cover is removed.
Mount the 1134 away from large metal objects
because it may impair performance. Do not
mount the 1134 inside a metal enclosure or install
in a drop ceiling.
1. With the cover removed, hold the 1134 in the
exact desired location.
2. Press the tamper switch to send data to the
panel and determine if communication is
confirmed or faulty.
Confirmed: If communication is
confirmed, for each press or release of the
tamper switch, the LED blinks
immediately on and immediately o.
Faulty: If communication is faulty, the
LED remains on for about 8seconds or
flashes multiple times in quick succession.
Relocate the 1134 or receiver until the LED
confirms clear communication.
FORM C RELAY
The 1134’s Form C relay draws up to 35mA of
current. Refer to the NC/C/NO (Dry Contact
Relay) and the Isolation Relay sections in this
document for more information.
PROGRAMMING CONNECTION
The 1134 provides a keypad programming
connection that allows you to use a standard
DMP LCD keypad for initial setup.
DRY/WET CONTACT
Apply power to the door relay (WET setting) or
leave it unpowered (DRY setting).