Programming Guide

1132 Installation and Programming Guide | Digital Monitoring Products 2
PROGRAM THE PANEL
Refer to the panel programming guide as needed. After completing each of the following steps, press CMD to
advance to the next prompt.
1. At a keypad, enter 6653 (PROG) to access the Programmer Menu.
2. At ZONE INFORMATION, enter the wireless zone number.
3. At *UNUSED*, enter the zone name.
4. At ZONE TYPE, press any select key or area and select the zone type.
5. At AREA NO, enter the area number.
6. At the NEXT ZN? prompt, select NO.
7. When WIRELESS? displays, select YES.
8. At SERIAL#, enter the eight‑digit device serial number.
9. At SUPRVSN TIME, enter a supervision time. Default is 240.
10. At the NEXT ZN? prompt, select YES if you are finished programming the zone. Select NO if you would like to
access additional programming options.
11. To save panel programming, go to STOP and press CMD.