Installation guide

XR150/XR350/XR550 Series Installation Guide Digital Monitoring Products
11
InstallatIon
Standby Battery Power Calculations Standby Current Alarm Current
736P POPIT Interface Module
Radionics Popex, POPITs, OctoPOPITs
Qty _______
Qty _______
x
x
25mA
___mA
______
______
Qty _______
Qty _______
x
x
25mA
___mA
______
______
738A Ademco Wireless Interface Module Qty _______ x 75mA ______ Qty _______ x 75mA ______
738Z Z-Wave Interface Module Qty _______ x 35mA ______ Qty _______ x 35mA ______
710 Bus Splitter/Repeater Module Qty _______ x 32mA ______ Qty _______ x 32mA ______
711 Zone Expansion Module
Active Zone (EOL Installed)
Qty _______
Qty _______
x
x
11mA
1.6mA
______
______
Qty _______
Qty _______
x
x
11mA
2mA*
______
______
714 Zone Expansion Module
Active Zones (EOL Installed)
Qty _______
Qty _______
x
x
7mA
1.6mA
______
______
Qty _______
Qty _______
x
x
7mA
2mA*
______
______
712-8 Zone Expansion Module
Active Zones (EOL Installed)
Qty _______
Qty _______
x
x
17mA
1.6mA
______
______
Qty _______
Qty _______
x
x
17mA
2mA*
______
______
714-8, 714-16 Zone Expansion Module
Active Zones (EOL Installed)
Qty _______
Qty _______
x
x
20mA
1.6mA
______
______
Qty _______
Qty _______
x
x
20mA
2mA*
______
______
715 Zone Expansion Module
Active Zones (EOL Installed)
2-Wire Smokes
Qty _______
Qty _______
Qty _______
x
x
x
7mA
4mA
.1mA
______
______
______
Qty _______
Qty _______
Qty _______
x
x
x
7mA
30mA*
.1mA
______
______
______
715-8, 715-16 Zone Expansion Modules
Active Zones (EOL Installed)
2-Wire Smokes
Qty _______
Qty _______
Qty _______
x
x
x
20mA
4mA
.1mA
______
______
______
Qty _______
Qty _______
Qty _______
x
x
x
20mA
30mA*
.1mA
______
______
______
716 Output Expansion Module
Active Form C Relays
Qty _______ x 13mA ______ Qty _______
Qty _______
x
x
13mA
12mA
______
______
717 Graphic Annunciator Module
Annunciator Outputs
Qty _______ x 10mA ______ Qty _______
Qty _______
x
x
10mA
1mA
______
______
521LX, 521LXT Smoke Detectors Qty _______ x 8.8mA ______ Qty _______ x 28mA* ______
2W-BLX, 2WT-BLX Smoke Detectors Qty _______ x 11mA ______ Qty _______ x 31mA* ______
COSMOD2W Module Qty _______ x 45mA ______ Qty _______ x 174mA*# ______
COSMO-2W Smoke and CO Detectors Qty _______ x 1mA ______ Qty _______ x 50mA*# ______
572 Indicator LED Qty _______ x 20mA ______ Qty _______ x 20mA ______
Aux. Powered Devices on Terminals 7 and 11
Other than Keypads and LX-Bus Modules
______mA ______mA
Sub-Totals this page
Sub-Total Standby
______mA Sub-Total Alarm ______mA
Sub-Totals from previous page
Sub-Total Standby
______mA Sub-Total Alarm ______mA
*Based on 10% of active zones in alarm Total Standby ______mA Total Alarm ______mA
# For systems that are not central station monitored, multiply alarm current by 12.
Total Standby______mA x number of Standby Hours needed
Total Alarm
______ =
______mA
Total
_______mA-hours
+_______mA-hours
_______mA-hours
X .001
= _______Amp-hrs Required
Refer to section 6.9 for standby battery selection.