PROGRAMMING GUIDE XR150/XR350/XR550 SERIES CONTROL PANEL
MODEL XR150/XR350/XR550 SERIES CONTROL PANEL PROGRAMMING GUIDE Contains programming Instructions for use with the Model XR150/XR350/XR550 Series Control Panels When using the XR150/XR350/XR550 Series panel for any listing organization’s approved methods, refer to this manual and the XR150/XR350/XR550 Series Installation Guide (LT-1233). These documents outline the installation and programming requirements of all applications for which the XR150/XR350/XR550 Series is approved.
TABLE OF CONTENTS Introduction.....................................................................................................1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14 1.15 Before you Begin............................................................................................................. 1 Getting Started................................................................................................................ 1 Encrypted Communications (XR550 with Encryption only).
TABLE OF CONTENTS 3.25 3.26 3.27 3.28 3.29 3.30 3.31 3.32 3.33 Alarm Switch................................................................................................................. 10 Duplicate Alarms............................................................................................................ 10 Alarm Reports................................................................................................................ 10 Supervisory/Trouble Reports...................................
TABLE OF CONTENTS 6.19.2 6.19.3 6.19.4 6.19.5 6.19.6 6.19.7 6.19.8 Zone 2 Bypass Time....................................................................................................... 17 Relock on Zone 2 Change?............................................................................................. 17 Activate Zone 3 Request to Exit....................................................................................... 17 Zone 3 REX Strike Time......................................................
TABLE OF CONTENTS 8.6 8.7 8.8 Code Change Reports..................................................................................................... 23 Access Keypads............................................................................................................. 23 Ambush........................................................................................................................ 23 System Options.....................................................................................
TABLE OF CONTENTS 11.5 11.6 11.7 11.8 11.9 11.10 11.11 11.12 11.13 11.14 11.15 11.16 11.17 11.18 11.19 11.20 11.21 Fire Trouble Output........................................................................................................ 30 Panic Alarm Output........................................................................................................ 30 Ambush Output............................................................................................................. 30 Entry Output.....
TABLE OF CONTENTS 16.5 16.6 16.7 16.8 16.9 Zone Reports................................................................................................................. 38 User Command Reports.................................................................................................. 38 Door Access Reports...................................................................................................... 38 Supervisory Reports.........................................................................
TABLE OF CONTENTS 18.11.3 18.11.4 18.11.5 18.11.6 18.11.7 18.11.8 18.11.9 18.11.10 18.11.11 18.11.12 18.12 18.13 18.14 18.15 18.16 18.17 18.18 18.19 18.20 18.21 18.22 18.23 18.24 18.25 18.26 18.27 18.28 18.29 18.30 Key Fob Supervision Time............................................................................................... 47 Number of Key Fob Buttons............................................................................................ 48 Key Fob Button Selection (Four Buttons).............
TABLE OF CONTENTS 22.9 22.10 22.11 22.12 22.12.1 22.12.2 22.13 22.14 User Profiles Record....................................................................................................... 61 Wireless Check-in and Supervision Definitions.................................................................. 61 Keypad Bus and LX-Bus Zone Type Descriptions............................................................... 61 Zone Type Specifications.................................................................
INTRODUCTION Introduction 1.1 Before you Begin This guide provides programming information for the DMP XR150/XR350/XR550 panel. After this Introduction, the remaining sections describe the functions of each programming menu item along with the available options. Before starting to program, we recommend that you read through the contents of this guide. The information contained here allows you to quickly learn the programming options and operational capabilities of the panel.
INTRODUCTION 1.3 Encrypted Communications (XR550 with Encryption only) Some installations require secure data communications. Use a unique passphrase to enable encrypted communications and provide a secure means for data communications. See Network Options. An XR550 panel with encryption communicates using 128-bit or 256-bit AES encryption.
INTRODUCTION 1.8 Keypads DMP offers multiple keypads in a variety of styles that provide programming capabilities. Each keypad and its operation are shown and described in the following sections.
INTRODUCTION Note: On Wireless, Thinline and Aqualite keypads, when instructed to press the first Select key, press the far left Select key; the second Select key is the second from the left; third Select key is second from the right; and the fourth Select key is the far right key. See Figure 7.
INTRODUCTION 1.12 Keypad Displays Current Programming Each programming option displayed at the keypad shows the currently selected option in the panel memory. These options are either shown as a number, a blank, or a NO or YES. To change a number or blank to a new number, press any top row Select key or touch any Select Area. The current option is replaced with a dash. Press the number(s) on the keypad you want to enter as the new number for that option.
INITIALIZATION Initialization NOTE: WHEN ANY PANEL PROGRAMMING IS CHANGED, THE STOP ROUTINE MUST BE RUN AND ‘SAVING PROGRAM’ MUST DISPLAY ON THE KEYPAD IN ORDER TO SAVE THE PROGRAMMING CHANGES. SEE SECTION 20.1. 2.1 INITIALIZATION Initialization This function allows you to clear selected parts of the panel program back to the factory defaults in preparation for system programming. Run the initialization function on all new installations.
COMMUNICATION 3.1 Communication COMMUNICATION Communication Configure the communication options for the panel. The information you program varies with the Communication Type you select. 3.2 ACCOUNT NO: 12345 3.3 XMIT DELAY: 3.4 PATH: - Communication Path 3.5 COMM TYPE: NONE Communication Type 30 NONE DD NET CID CELL 3.6 PATH TYPE: BACKUP PRIMARY BACKUP 3.7 TEST RPT:YES NO YES DEFER 3.
COMMUNICATION 3.9 TEST DAY: SUN Test Day 3.10 TEST TIME: 0:00 AM Test Time 3.11 CHECKIN: Use this option to set the day of the Test Report. This option appears only when Test Report is Yes, Test Frequency is Day and a multiple of seven. Press the COMMAND key to display the first four days of the week. Press the COMMAND key to display the last three days. Select the day of the week to send the test report. Default is Sunday. NO YES CHECKIN: NO YES RND ADPT CHECKIN: ADP3 CHECKIN MINS: 200 3.
COMMUNICATION 3.17 SECOND PHONE NO. Second Telephone Number 3.18 ADVANCED? NO Advanced Programming 3.19 FIRST GPRS APN SECURECOM400 - First GPRS APN SECOND GPRS APN SECURECOM400 - Second GPRS APN 3.20 FAIL TEST HRS: 3.21 PROTOCOL:TCP 3.22 RETRY SECONDS: 3.23 SUB CODE: NO NO 3.24 893A: YES The panel dials the second number when two successive tries using the first number fail.
COMMUNICATION Unrestored System Recall Test) are sent to the receiver at the frequency programmed in Test Frequency, alternating between the first and second phone line. For example, a DD path with an 893A module set for daily test report frequency sends a test report through phone line 1 one day and phone line 2 the next day. If the 893A option is set to YES, enter up to a 3-digit prefix to be dialed before the second phone number.
COMMUNICATION 3.32 3.33 SEND COMM TRBL: NO YES SEND PATH INFO: NO YES Send Communication Trouble This option displays for each path and determines if and how communication trouble on the path is sent to the receiver. A trouble message indicates both the path number and communication type that failed. Default is Yes. Send Path Information This option displays for each path and if YES, each panel message includes path information such as path number, communication type, and path type.
NETWORK OPTIONS Network Options (Network or Encryption Only) Network Options are provided to define the network configuration for the panel. This information will be used during communication of messages via network. Note: IP addresses and port numbers may need to be assigned by the network administrator. When entering an IP, Gateway, or Subnet Mask address be sure to enter all 12 digits and leave out the periods. For example, IP address 192.168.000.250 is entered as 192168000250. 4.1 DHCP 4.
MESSAGING SETUP Messaging Setup 5.1 MESSAGING SETUP Messaging Setup 5.2 ENABLE MESSAGING NO YES Enable Messaging 5.3 SYSTEM NAME - System Name 5.4 DESTINATION 1 Destination 1 5.6 5.7 5.8 Select YES to allow the panel to send messages to three programmed destinations. Default is NO. Enter a unique name for the panel. The panel name is used as the sender of the message. The text entered is displayed with initial caps. If this field is left blank, the panel account number is sent.
DEVICE SETUP 6.1 Device Setup DEVICE SETUP Device Setup This section allows you to define the panels physical configuration. You can install and address up to sixteen supervised devices on the keypad data bus. 6.2 DEVICE NO:- Device Number 6.3 * UNUSED * Device Name 6.4 TYPE: KEYPAD DOOR KPD FI EXP Device Type 6.5 DEVICE COMM TYPE KPD-BUS Device Communication Type Enter the address of the device you are programming. The valid range is 1-16.
DEVICE SETUP 6.8 EGRESS AREAS: Egress Areas 6.9 DISPLAY AREAS: Display Areas *1 *5 *2 *6 *3 *7 Press the COMMAND key to program Egress Areas. To select an area, enter the area number using the digit keys on the keypad. When an area is selected, an asterisk appears next to the area number. Enter the number again to deselect the area. Press COMMAND to display the next set of areas. Refer to the Multiple Displays section at the beginning of this document.
DEVICE SETUP When an area(s) is chosen, the following displays are allowed: • Armed Status of the selected area(s) • Zone Alarms and troubles for burglary (NT, DY, EX, A1, A2) type zones assigned to the selected area(s) • Late to Close status of the selected area(s) • Zone Status (normal/fault) of zones that are assigned to the selected area(s) Options and Actions Not Affected The following options are not affected by the Display Areas operation.
DEVICE SETUP Note: When OVERRIDE is YES and there are no areas programmed in ACCESS AREAS, the door schedule for that device does not work. Either set OVERRIDE to NO or enter an area number in ACCESS AREAS. 6.16 AUTO FORCE ARM DEVICE? NO YES Auto Force Arm Device? 6.17 DOOR REAL-TIME STATUS? NO YES Door Real-Time Status? 6.18 SEND DOOR FORCED MESSAGE? NO YES Send Door Forced Message? 6.19 PROGRAM 734 OPTIONS? NO YES Program 734/734N Options 6.19.
DEVICE SETUP The 734/734N/734N-WiFi module provides a bypass-only option for REX on Zone 3. When Zone 3 opens from a normal state, only a bypass occurs: the on-board relay does not activate. This bypass-only option uses two methods of REX. The first REX device provides the programmed Bypass entry/exit timer. The second REX device, or manual device such as a door knob, unlocks the door. An example of the bypass-only configuration is a door to an office that is locked 24 hours a day.
DEVICE SETUP 6.19.12 USER CODE LENGTH: 6.19.13 REQUIRE SITE CODE? NO YES 6.19.13.1 SITE CODE 1: - SITE CODE 1: (1-65,535) 127 6.19.14 6.19.15 User Code Length 16 Define the number of User Code bits. Press any top row Select key to enter a custom number. On a 734 module, custom numbers can only be between 16-40. On a 734N/734N-WiFi module, custom numbers can be between 1-255. The default is 16. Require Site Code Press the top row Select key under YES to use a site code.
REMOTE OPTIONS 7.1 Remote Options Remote Options REMOTE OPTIONS This section allows you to enter the information needed for Remote Command/Remote Programming operation. 7.2 REMOTE KEY: Remote Key 7.3 REMOTE DISARM? NO YES Remote Disarm 7.4 ARMED ANSWER RINGS: This option allows you to enter a code of up to 16 characters. The Remote Link™ program must give the correct key to the panel before being allowed any remote functions.
REMOTE OPTIONS 7.9 MANUFACTURER AUTH? NO YES Manufacturer Authorization 7.10 ALLOW NETWORK REMOTE? NO YES Allow Network Remote 7.10.1 NETWORK PROG PORT: 2001 Network Programming Port 7.10.2 ENCRYPT NETWORK REMOTE? NO YES Encrypt Network Remote 7.11 ALLOW CELL REMOTE? NO YES Allow Cellular Remote 7.11.
REMOTE OPTIONS 7.12.5 ENTRE BACKUP TCP PORT: 2001 7.12.6 ENTRE CHECKIN MINUTES: 7.12.7 ENTRE PASSPHRASE 7.13 0 Entré Passphrase SEND LOCAL Send Local Changes SEND LOCAL NO NET DD REMOTE CHANGE IP 000.000.000.000 7.13.2 REMOTE CHANGE PORT: 2002 7.13.3 REMOTE PHONE NO. - 7.14 Entré Checkin Select the rate at which check-in messages are sent over the Entré connection. Select 0 (zero) to disable check in messages. Range is 0, 3-240 minutes. Default is 0.
SYSTEM REPORTS System Reports 8.1 SYSTEM REPORTS 8.2 ABORT NO YES 8.3 RESTORAL: NO YES YES DISARM System Reports Select specific system reports the panel sends to the receiver. Abort Report YES allows the panel to send an alarm abort report to the receiver any time an area is disarmed during Transmit Delay before an alarm report is sent and the Bell Cutoff Time has not expired.
SYSTEM OPTIONS System Options 9.1 9.2 System Options SYSTEM OPTIONS This section allows you to select system-wide parameters. SYSTEM: AREA AREA A/P H/A GST System This option allows you to program how the areas operate for arming and disarming. The options you can choose are listed below: AREA - All 32 areas can be programmed and operated independently. ALL/PERIMETER - Area 1 is the Perimeter and Area 2 is the Interior.
SYSTEM OPTIONS 9.7 RETARD DELAY: 10 9.8 PWR FAIL HRS: 1 Power Fail Delay 9.9 SWGRBYPS TRIPS: 2 Swinger Bypass Trips 9.10 RST SBYP NO YES Reset Swinger Bypass 9.11 ZN ACTY HRS: Zone Activity Hours 9.12 TIME CHG NO YES HRS FROM GMT: GMT 0 6 Zone Retard Delay Enter the retard time assigned to Fire, Supervisory, Auxiliary 1, Auxiliary 2, Arming, and Panic type zones. The retard delay only functions when the zone is shorted.
SYSTEM OPTIONS 9.13 LATCH SV 9.14 PROG LANGUAGE PRI LANG: ENG NO YES FRN SEC LANG: NONE NONE ENG SPN FRN 9.15 ENG ENGLSH SPN Press the COMMAND key to select the programming language. Any changes in PROG LANGUAGE do not take effect until the STOP routine completes. The current primary programming language displays. The default language is English. Press a Select key to change the primary programming language. Select the primary programming language.
SYSTEM OPTIONS 9.18 9.19 DETECT WIRELESS JAMMING: NO YES WLS AUDIBLE: DAY WIRELESS AUDIBLE ANY DAY MIN Detect Wireless Jamming This option displays when the House Code entered is for a DMP 1100 Series Wireless system (1-50). When enabled and the wireless receiver detects jamming, a trouble or alarm message displays in the Status List and is sent to the central station receiver. Select YES to enable jamming messages to display in the Status List. Select NO to disable jamming messages. Default is NO.
SYSTEM OPTIONS 9.25 9.26 USE FALSE ALARM QUESTION NO YES ALLOW OWN USER CODE CHG? NO YES Use False Alarm Question This option allows users to investigate a burglary alarm prior to disarming the system and send an Alarm Verified or Alarm Cancelled message to the Central Station. Select YES to display IS THIS A FALSE ALARM? NO YES when a burglar alarm occurs. Select NO to display CANCEL VERIFY. Default is YES.
BELL OPTIONS Bell Options 10.1 Bell Options This section allows you to program the panel bell output functions. BELL OPTIONS 10.2 Bell Cutoff Time BELL CUTOFF: 15 10.3 Automatic Bell Test BELL TST 10.4 10.5 10.5.1 10.5.2 10.5.3 10.5.4 10.5.5 10.5.6 10.5.7 Enter the maximum time from 1 to 99 minutes the Bell Output remains on. If the area is disarmed, the cutoff time resets. Enter 0 (zero) to provide continuous bell output. The default is 15 minutes.
OUTPUT OPTIONS 11.1 11.2.1 11.2.2 11.3 11.4 11.5 11.6 11.7 Output Options OUTPUT OPTIONS CO OUTS: - - - - - - CUTOFF TIME: 0 COMM FAIL OUT: 0 FIRE ALR OUT: 0 FIRE TRB OUT: 0 PANIC ALM OUT: 0 AMBUSH OUT: 0 Digital Monitoring Products 30 Output Options This section allows you to program panel output options. The panel provides two Form C relays (1 and 2) and four switched ground (open collector) outputs numbered 3 to 6.
OUTPUT OPTIONS 11.8 Entry Output ENTRY OUT: 0 11.9 11.10 11.11 11.12 11.13 11.14 11.15 11.16 11.17 11.18 BEG EXIT OUT: 0 END EXIT OUT: 0 READY OUT: 0 DISARMED OUT: 0 PH TRBL OUT: 0 LATE CLS OUT: 0 DVC FAIL OUT: 0 SNSR RST OUT: 0 CLS WAIT OUT: 0 ARM-ALARM OUT: 0 Enter the output/Favorite number to turn on at the start of the entry delay time. The output turns off when the area is disarmed or the entry delay time expires. Enter 0 (zero) to disable.
OUTPUT OPTIONS 11.19 SUPV ALM OUT: 0 Supervisory Alarm Output Enter the output/Favorite number to turn on when a supervisory zone type is placed into an alarm. The output turns off when all supervisory type zones are restored to normal. Enter 0 (zero) to disable. Default is 0. 11.20 HEAT SAVER TEMPERATURE: 0 Heat Saver Temperature 11.
OUTPUT INFORMATION Output Information 12.1 12.2 12.3 12.4 12.5 Output Information OUTPUT INFO OUTPUT NO. This section allows you to program wireless outputs and name wired outputs. XXX Output Number Enter an output number. Entry range is 1 to 6, 450 to 474, 480 to 499, 500 to 999. In order for wireless output troubles to display at a keypad, the keypad address must be specified at the Auxiliary 1 Zones option in the Status List programming.
OUTPUT GROUPS Output Groups 13.1 Output Groups OUTPUT GROUPS This function allows you to assign outputs to groups. Output groups can be assigned to other areas of programming such as Output Options or Alarm Action of Zone Information, just like single outputs are assigned. This allows the entire group of outputs to turn on and off as required by the programming option. 13.2 GROUP NO: - Group Number 13.3 GROUP NAME X X Group Name 13.
MENU DISPLAY Menu Display 14.1 14.2 Menu Display MENU DISPLAY Menu Display allows you to select at which keypad addresses the user can access the following functions. To select a keypad, enter the device number (keypad address) using the digit keys on the keypad. When a keypad is selected, an asterisk appears next to the keypad address. Enter the number again to deselect the keypad. Press the COMMAND key to display the next set of keypads (9 through 16).
STATUS LIST Status List 15.1 STATUS LIST 15.2 DISPLAY KEYPADS: Display Keypads 15.3 SYSTEM TROUBLES: System Monitor Troubles *1 *5 *2 *6 *3 *7 Status List This function allows you to select the zone alarms and troubles, and system monitor troubles displayed at the keypads. The Status List function operates automatically when the keypad is not performing any other function. The keypad stays in the Status List until the user arms or disarms or selects a menu option.
STATUS LIST 15.6 SPRVISORY ZONES: Supervisory Zones 15.7 PANIC ZONES: Panic Zones 15.8 EMERGENCY ZONES: Emergency Zones 15.9 AUX 1 ZONES: Auxiliary 1 Zones 15.10 AUX 2 ZONES: 15.11 COMM PATH TRBL: NO YES ALL Specifies the keypad addresses (1 through 16) where all supervisory zone alarms and troubles display. Supervisory zones are entered in the status list and sound the keypad buzzer until a valid user code is entered at any keypad address.
PC LOG REPORTS PC Log Reports 16.1 16.2 PC LOG REPORTS NET IP ADDRESS 000.000.000.000 PC Log Reports This section allows you to program the types of PC Log Reports the panel sends through the J1 Ethernet Port directly on the panel. The reports include information such as the type of activity, time and date of the activity, and user name and number. These data reports can be accessed from a PC using the Advanced Reporting Module.
AREA INFORMATION 17.1 17.2 Area Information AREA INFORMATION EXIT DELAY: 60 Area Information Allows you to assign functions to the different areas in the system. All non-24-hour zones must be assigned to an active area. See Zone Information. You activate an area by assigning it a name. See Area Name. A name is given to each active area in place of a number to assist the user during arming and disarming. When only areas one to eight are used, the Armed Status display is 1 2 3 4 5 6 7 8.
AREA INFORMATION 17.7 ANY BYPS NO YES Any Bypass 17.8 AREA SCH NO YES Area Schedules 17.9 EARLY AMBUSH: Early Morning Ambush (Network panels only) 17.10 AREA NO: - 17.10.1 17.10.2 17.11 0 BDRM Select YES to allow each area to follow individual sets of area schedules programmed in the User Menu. Select NO for all areas to follow only one set of schedules in the User Menu. See the panel User Guide to add schedules to the panel.
AREA INFORMATION 17.13 AUTO ARM NO YES 17.14 BAD ZONES: BYP BYPFORC REF 17.15 AUTO DIS NO YES 17.16 ARMED OUTPUT: 0 17.17 LATE OUTPUT: 0 17.18 LATE/ARM DLY: 60 17.19 BANK/SAF NO YES 17.20 COMMON NO YES Automatic Arming Select YES to allow this area to arm automatically according to permanent, temporary, or extended schedules. If no schedules are programmed, the area auto arms every hour.
AREA INFORMATION 17.21 ARM FIRST 17.22 TWO MAN NO YES NO YES Digital Monitoring Products 42 Arm First Area Select YES to enable this area to operate as an Arm First area. This area is automatically armed when any non-Arm First area assigned to the same keypad is armed but does not disarm when other areas become disarmed. Assign areas to keypads using the Display Areas option in Device Setup programming. You can have multiple Arm First areas in a system and divide them among keypads if needed.
ZONE INFORMATION Zone Information 18.1 18.2 ZONE INFORMATION ZONE NO: - Zone Information Zone Information allows you to define the operation of each protection zone used in the system. All protection zones, whether located on a panel, Security Command keypad, or zone expander are programmed the same way. Zone Number Enter the number of the zone you intend to program. Available zone numbers are shown in the table below.
ZONE INFORMATION 18.4 ZONE TYPE: BLANK -FI A1 18.5 NT PN A2 DY EM FV EX SV AR PERIMETER INT PERIM INT 18.6 18.7 BDRM PERIM FIRE BELL OUT: ARM/DIS AREAS Digital Monitoring Products 44 The Zone Type defines the panel response to the zone being opened or shorted. This is called the Alarm Action. There are up to 13 possible alarm action responses depending on the zone type and any restrictions it may have. See the Zone Type chart in the Appendix.
ZONE INFORMATION ARM AREAS: PERIM PERIM ALL HOME SLEEP AWAY 18.8 Style STYLE: TGL ARM DIS STEP NEXT ZN? NO YES MNT 18.9 To visually indicate the armed state of the area(s), you can assign an Armed Output to individual areas and use remote LEDs at the keyswitch. The LED turns on or off to indicate to the user the armed state of the area(s). In an All/Perimeter or Home/Sleep/Away system, this option specifies the areas to be armed by the Arming Type zone.
ZONE INFORMATION DMP Wireless For a DMP 1100X Wireless Receiver set the House Code from 1 to 50. See House Code programming in System Options. Zones 500 through 999 can be programmed as Wireless zones. Briefly reset the panel using the J16 jumper to activate Wireless operation. Refer to the XR150/XR350/XR550 Series Installation Guide (LT-1233). For an 1100 Series Key Fob see section 18.11. NOTE: All wireless programming is stored in the panel.
ZONE INFORMATION The 3 minute supervision time is only available for zone types of Fire (FI), Fire Verify (FV), and Supervisory (SV). Note: When the panel is reset or a receiver is installed or powered down and powered up, the supervision timer restarts for all wireless zones. 18.10.4 LED OPERATION NO YES LED Operation 18.10.5 DISARM DISABLE NO YES Disarm/Disable 18.10.6 WIRELESS PIR PULSE COUNT: 18.10.7 WIRELESS PIR SENSITIVITY: LOW PIR Sensitivity 18.10.
ZONE INFORMATION 18.11.4 NO. OF KEY FOB BUTTONS: X Number of Key Fob Buttons Enter the number of buttons (1, 2, or 4) on the key fob being programmed. Note: If the key fob is a one-button model, programming continues at the Button Action section. Default button assignment for one-button key fobs is a Panic Alarm (PN) with no output assigned. 18.11.5 BUTTON: TOP BTM LFT RGT Key Fob Button Selection (Four Buttons) 18.11.6 BUTTON: TOP BTM Key Fob Button Selection (Two Buttons) 18.11.
ZONE INFORMATION Note: When more areas are selected at Arm/Disarm Areas than are authorized in the ARM AREAS: PERIM 18.11.10 OUTPUT NO: XXX 18.11.11 OUTPUT ACTION: yyy: XXXXXXXX OUTPUT ACTION? STD PLS MOM TGL OUTPUT ACTION? OFF 18.11.12 NEXT ZONE NO YES User Profile, in the future the user can be given access authority to additional areas through the User Profile without requiring additional panel programming to select Arm/ Disarm Areas.
ZONE INFORMATION 18.12 ALARM ACTION . . . . 18.13 DISARMED OPEN 18.14 MSG: Alarm Action This option allows you to change any Zone Type standard definitions. When the Zone Type is specified, the Alarm Action for that zone is stored in memory. If the Zone Type is Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 it is a non‑24‑hour zone and the Alarm Action programing begins with Disarmed Open.
ZONE INFORMATION STD PLS MOM FOLW 18.17 SWGR BYP 18.18 PREWARN KEYPADS: 18.19 ENTRY DELAY: 18.20 RETARD NO YES 18.21 PRESGNL KEYPADS: 18.22 FAST RSP NO YES NO YES STEADY - The output is turned on and remains on until the area is disarmed, an output cutoff time expires, or the output is reset from the keypad menu. PULSE - The output alternates one second on and one second off. Note: The pulsing rate for a Model 716 relay attached to the LX-Bus is 1.6 seconds.
ZONE INFORMATION 18.23 CRS ZONE NO YES 18.24 PRIORITY NO YES 18.25 FIRE PANEL SLAVE INPUT: NO YES 18.26 FOLLOW AREA: 18.27 18.28 18.29 18.30 0 ZONE REAL-TIME STATUS NO YES TRAFFIC COUNT NO Priority Select YES to provide additional protection for the premises by requiring this zone to be in a normal condition before its assigned area can be armed.
STOP Stop 19.1 STOP Stop Save Programming WHEN ANY PANEL PROGRAMMING IS CHANGED, THE STOP ROUTINE MUST BE RUN AND ‘SAVING PROGRAM’ MUST DISPLAY ON THE KEYPAD IN ORDER TO SAVE THE PROGRAMMING CHANGES. At the STOP option, pressing any Select key allows you to exit the Programmer function of the panel. When selected, the panel performs an internal reset and exits the programmer.
FEATURE UPGRADE Feature Upgrade 21.1 FEATURE UPGRADE ENTER KEY - Feature Upgrade In the Programming Menu, pressing COMMAND at the SET LOCKOUT CODE option displays FEATURE UPGRADE. This allows you to enable additional features in the panel. Press any top row Select key to display the first available feature. ENABLED or DISABLED displays indicating whether this feature is currently used in this panel. Press the COMMAND key to display additional feature(s).
APPENDIX Appendix 22.1 False Alarm Reduction System Recently Armed report The System Recently Armed report (S78) is sent to the receiver when a burglary zone goes into alarm within two minutes of the system being armed. 22.2 Diagnostics Function The panel contains a Diagnostics function that allows you to test the communication integrity of the LX-Bus™, identify individual zones, and also display the present electrical state of any zone.
APPENDIX MAC Address Short for Media Access Control address. This hardware address uniquely identifies each network node. Not to be confused with an IP address, which is assignable. In the Diagnostics function, the MAC address is the panel on-board network hardware address. Press any top row Select key to display the panel MAC address. Press the COMMAND key to view the next option. Serial Number This number is the network communicator serial number.
APPENDIX Activate Cell (263C Only) Note: ( Version 109 or higher firmware) If the 263C Cellular Communicator has not been previously activated, Automatic Cellular Activation is performed when the panel powers up or is reset. Activate Cell (discussed below) is only necessary when Automatic Cellular Activation is not successful and communication was not established.
APPENDIX Note: The panel makes ten attempts to reach the receiver. While attempting to contact the receiver, if the panel needs to send an alarm report, the panel stops dialing and uses the phone line to send its report. TEST: The panel allows you to perform a Communication Status Test on each component of the panel’s cellular or network communication paths. While the Status List displays, enter 984 and press the COMMAND key. The keypad display changes to NBR TEST PICKUP.
APPENDIX Note: During the Walk Test, trip each zone device or button on the system for 1 to 2 seconds. You do NOT have to hold the zones for 2 seconds in normal mode for PN type zones. You are only required to hold the panic during the Walk Test because the zone takes additional time to report when the system is in test mode. WLS (Wireless Check-in Test) - Select WLS to automatically test wireless transmitter communications.
APPENDIX ZONE: 10 SOUTH LOBBY 22.5 -FAIL Failed Zones Display For each zone that did not trip (failed), except key fobs, at least once during the Walk Test, all keypads with matching Display Areas programming display the zone name and number and buzz for one second.
APPENDIX Always make sure that at least one administrator in your system has a profile with all authorities and areas. First Access/Second Access - Each profile may be assigned two schedules to allow or restrict access and disarming times. 22.
APPENDIX PN (Panic zone) Used for connecting to mechanical devices that allow a user to signal an emergency alarm. Panic zones can provide either a silent or audible alarm with or without reporting to a central station receiver. EM (Emergency zone) These are used for reporting medical or other non-panic emergencies to the central station receiver. SV (Supervisory zone) Used to provide 24-hour zone supervision to devices associated with fire systems.
APPENDIX 22.12.1 Keypad Bus Zone Type Defaults These are complete spellings of the abbreviations used for the zone types, such as Night and Exit. Type - These are the abbreviations used for the zone types, such as NT and EX. Area - For an Area or Home/Sleep/Away with Guest system this is 1 to 32. For an All/Perimeter or Home/ Sleep/Away system, this is the Interior, Bedroom, or Perimeter. Select the area for NT, DY, EX, A1, A2, and AR types. Fire Bell Out - Only available for FI, FV, and SV zones.
APPENDIX Wireless + + + N N N + + N N 1 1-16 S S 0 0 0 0 A A A A T T 0 0 S S – T – – T – Low Low Low Low Low Low Low Low Low Low Low 4 4 4 4 4 4 4 4 4 4 4 1 to 32 0 Output * or 0 1101 Contact Zone Type Defaults Assign Retard and Presignal for FI, SV, A1, A2, and PN only. 0 1101 EXT Contact N/O? NT DY EX FI PN EM SV A1 A2 FV AR =Zone functions not available.
APPENDIX 22.13 Common Keypad Messages There are several common keypad messages that the keypad displays to inform the technician and end‑user. The common messages are described below. Possible solutions are also provided.
22.
XR150/XR350/XR550 Series Programming Guide Digital Monitoring Products 67
Export Control 800 - 641 - 4282 The XR550 with encryption uses AES encryption and any export beyond the United States must be in accordance with Export Administration Regulations. INTRUSION • FIRE • ACCESS • NETWORKS www.dmp.com 2500 North Partnership Boulevard Designed, Engineered and Assembled in U.S.A.