User's Manual

8
3.6 Deleting Wireless Devices
To remove a wireless device from the system, follow the guideline for adding a wireless
device. Program the ESN as [000000]. The wireless device for the zone will be removed.
Now that you have enrolled all the wireless devices, you will need to program the system
to work properly with the devices. See section 4 for more information.
Section 4: Other Programming
4.1 Program Zones and Partitions
Now that you have enrolled the wireless devices, you should complete all zone program-
ming on the system. Although the exact programming required varies depending on which
control panel the RF5108-433 is connected to, you should check that the following
programming areas are completed correctly for each wireless zone:
Enable zones and/or assign zones to one or more partitions (programming sections
[201]-[209], [201]-[265] for PC5020).
Program the definition for each zone (programming sections [001]-[004]).
NOTE: WLS906 wireless smoke detectors must be assigned to zones defined as Delay
24-hr fire (wireless) [87] or Standard 24-hr fire (wireless) [88] for proper supervision.
Enable the wireless zone attribute for each wireless zone (PC580, PC585, PC1555,
PC1565, PC5020, PC501X v2.0 and higher only) (sections [101]-[132]).
See your system
Installation Manual
, for more information on each of the above program-
ming sections.
4.2 Enable RF5108-433 Supervision
The control panel will supervise the RF5108-433 receiver via the Keybus after at least one
device has been enrolled on the module (see section 3.2 “Enrolling Wireless Devices”). The
RF5108-433 is supervised as a PC5132.
To activate module supervision, after you enroll the first device(s):
1. Exit and then re-enter Installer Programming.
2. Enter programming section [902]. Wait approximately 1 minute.
3. To exit press [#].
The system will generate a General System Supervisory trouble if the module is removed
from the Keybus. If you need to remove the RF5108-433 module from an existing system,
you will have to disable supervision of the RF5108-433.
NOTE: Deleting all devices from the RF5108-433 or defaulting the RF5108-433 will cause
a PC5132 supervisory fault
To disable RF5108-433 supervision:
1. Disconnect the RF5108-433 from the Keybus
2. Enter [][8][Installer’s Code]
3. Enter [902]. The control panel will clear all supervision and re-scan the system for
connected modules. The scan will take approximately one minute.
4. To exit press [#].
W I R E L E S S D E V I C E S