Technical data
Linkage with PLC
CP 486 ⋅ 00/14 VIPA GmbH 105
Example for calling up FB2 in OB21:
Module#OB21
BIB
0000 ;SPA FB 2
NAME #SYNCHRON
SSNR =KY +32
WART =KF +0
PAFE =MB 98
0005 ;BE
Transfer parameters:
SSNR: KF Number of basic bank
WART: = 0 FB-SYNCHRON does not wait until every single bank is
synchronized by CP
>< 0 FB-SYNCHRON waits at every single bank until the CP
has synchronized this bank
PAFE: BY Error acknowledgement message of handling module
= 0 no error occurred
>< 0 error occurred:
3 basic bank number is not divisible by 8.
Scratch markers used: MB200-MB255