,6.3.2 Parameterization of Handling Modules:
The handling modules SEND (FB3), CONTROL (FB4), FETCH (FB5) and RECEIVE (FB6) are
parameterized as follows:
6.3.2.1 Handling Module SEND (FB3, Relative Bank Number: 1):
This handling module transfers a data block of up to 504 words from a DB to the CP486. For
identification purposes a job number is also sent to the CP486. The handling module supplies the
result by means of a display word in a marker word to the application program. Parameterization
errors are signalled via a marker byte. The handling module is directly and indirectly
parameterizable:
Module#FB3
BSTNAME #SEND
BIB
BEZ #INSS D:KY
BEZ #A-NR D:KY
BEZ #DOSP D:KY
BEZ #ANZW D:KY
BEZ #QT/N D:KY
BEZ #QANF D:KF
BEZ #QLAE D:KF
BEZ #PAFE A:BY
Transfer parameters:
INSS: D KY IN Code if direct or indirect parameterization
= 0 direct parameterization via formal operands
>< 0 indirect parameterization - transfer parameters are filed
in opened DB
SS number of basic bank (must be divisible by 8)
A-NR: D KY If direct parameterization left byte has the job number
(1..127) and right byte the function number for CP-driver.
If indirect parameterization, A-NR has the DW-no, from which
on the parameters are in the open DB. Thereby the content
of the parameter is evaluated as word.
DOSP: D KY DOS-parameter which is also transferred at certain functions.
It can be a handle, an access or a drive-number.
ANZW: D KY left byte: reserve
right byte: contains the MW-no. where the display word is
to be stored (permitted are MW0..MW198)
Display word can have following information at SEND status:
Bit .0 =0
.1 job runs (job transferred without errors)
.2 =0
.3 job finished with error
4F-Nr. 2raisedto0
2raisedto1
2raisedto2
2raisedto3