Linkage with PLC
118 VIPA GmbH CP486 00/14
Error acknowledge message of handling module:
= 0 no error occurred
><0 error occurred, error number in PAFE-Byte:
3 basic bank number is not divisible by 8
5 bank is not synchronized yet by the CP
10 invalid job number (out of 1...127)
12 no DB open for indirect parameterization
16 DB for indirect parameterization too short
20 invalid marker word no. for ANZW (out of 0...198)
Attenttion:
If the bank number of the CP does not coincide with the number parameterized in this module, the
CPU goes in stop with QVZ!
Parameter storage in a DB if parameterization is indirect:
DL DR
A-NR points to the beginning
INSS
A-NR F-NR
DOSP
LAE
ANZW
PAFE is not parameterizable indirectly
0 can be parameterized at all other formal operands (SS, DOSP, LAE, ANZW) because these are
not evaluated at indirect parameterization.
Scratch markers used: MB200-255